Table 22:
Settings for calibration parameters
Setting
Short Description
Selected
value
Comments
IMagComp5
Magnitude factor to calibrate
current at 5% of In
0.00
IMagComp30
Magnitude factor to calibrate
current at 30% of In
0.00
IMagComp100
Magnitude factor to calibrate
current at 100% of In
0.00
VAmpComp5
Magnitude factor to calibrate
voltage at 5% of Vn
0.00
VMagComp30
Magnitude factor to calibrate
voltage at 30% of Vn
0.00
VMagComp100
Magnitude factor to calibrate
voltage at 100% of Vn
0.00
IAngComp5
Angle calibration for current at 5%
of In
0.00
IAngComp30
Angle pre-calibration for current
at 30% of In
0.00
IAngComp100
Angle pre-calibration for current
at 100% of In
0.00
14.5
Event counter CNTGGIO
14.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Event counter
CNTGGIO
S00946 V1 EN
-
14.5.2
Application
Event counter (CNTGGIO) has six counters which are used for storing the number of
times each counter has been activated. CNTGGIO can be used to count how many times
a specific function, for example the tripping logic, has issued a trip signal. All six counters
have a common blocking and resetting feature.
14.5.3
Setting guidelines
Operation:
Sets the operation of Event counter (CNTGGIO)
Enabled
or
Disabled
.
1MRK 506 334-UUS A
Section 14
Monitoring
437
Application manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Страница 2: ......
Страница 30: ...24...
Страница 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Страница 110: ...104...
Страница 260: ...254...
Страница 274: ...268...
Страница 280: ...274...
Страница 396: ...390...
Страница 494: ...488...
Страница 506: ...500...
Страница 515: ...509...