The operation from local HMI is from select or indication buttons (32 positions). Typical
applications are: Select operating modes for e.g. Auto reclose, Energizing check, Ground
fault protection (IN,UN). The output integer can be connected to an Integer to Binary
function block to give the position as a boolean for use in the configuration.
11.6.3
Setting guidelines
The following settings are available for the Logic rotating switch for function selection
and LHMI presentation (SLGGIO) function:
Operation
: Sets the operation of the function
Enabled
or
Disabled
.
NrPos
: Sets the number of positions in the switch (max. 32). This setting influence the
behavior of the switch when changes from the last to the first position.
OutType
:
Steady
or
Pulsed
.
tPulse
: In case of a pulsed output, it gives the length of the pulse (in seconds).
tDelay
: The delay between the UP or DOWN activation signal positive front and the
output activation.
StopAtExtremes
: Sets the behavior of the switch at the end positions – if set to
Disabled
,
when pressing UP while on first position, the switch will jump to the last position; when
pressing DOWN at the last position, the switch will jump to the first position; when set to
Enabled
, no jump will be allowed.
11.7
Selector mini switch VSGGIO
11.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Selector mini switch
VSGGIO
-
-
11.7.2
Application
Selector mini switch (VSGGIO) function is a multipurpose function used in the
configuration tool in PCM600 for a variety of applications, as a general purpose switch.
VSGGIO can be used for both acquiring an external switch position (through the IPOS1
and the IPOS2 inputs) and represent it through the single line diagram symbols (or use it
in the configuration through the outputs POS1 and POS2) as well as, a command function
Section 11
1MRK 506 334-UUS A
Control
386
Application manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Страница 2: ......
Страница 30: ...24...
Страница 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Страница 110: ...104...
Страница 260: ...254...
Страница 274: ...268...
Страница 280: ...274...
Страница 396: ...390...
Страница 494: ...488...
Страница 506: ...500...
Страница 515: ...509...