8
X1
Zm
6.2.3.2
Resistive reach with load encroachment characteristic
The procedure for calculating the settings for the load encroachment consist basically to
define the load angle
LdAngle
, the blinder
RLdFwd
in forward direction and blinder
RLdRev
in reverse direction, as shown in figure
.
R
X
RLdFwd
RLdRev
LdAngle
LdAngle
LdAngle
en05000226_ansi.vsd
LdAngle
ANSI05000226 V1 EN
Figure 69:
Load encroachment characteristic
The load angle
LdAngle
is the same in forward and reverse direction, so it could be suitable
to begin to calculate the setting for that parameter. Set the parameter to the maximum
possible load angle at maximum active load. A value bigger than 20° must be used.
The blinder in forward direction,
RLdFwd
, can be calculated according to equation
=
×
2
min
0.8
exp max
RLdFwd
P
V
where:
Pexp max is the maximum exporting active power
Vmin
is the minimum voltage for which the Pexp max occurs
0.8
is a security factor to ensure that the setting of
RLdFwd can be lesser than the calculated minimal
resistive load.
1MRK 506 334-UUS A
Section 6
Impedance protection
145
Application manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Страница 2: ......
Страница 30: ...24...
Страница 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Страница 110: ...104...
Страница 260: ...254...
Страница 274: ...268...
Страница 280: ...274...
Страница 396: ...390...
Страница 494: ...488...
Страница 506: ...500...
Страница 515: ...509...