Set value
Mode
Formula used for complex power calculation
CA
*
*
(
)
CA
C
A
S V
I
I
=
×
-
EQUATION2060-ANSI V1 EN
(Equation 158)
A
*
3
A
A
S
V
I
= ×
×
EQUATION2061-ANSI V1 EN
(Equation 159)
B
*
3
B
B
S
V
I
= ×
×
EQUATION2062-ANSI V1 EN
(Equation 160)
C
*
3
C
C
S
V
I
= ×
×
EQUATION2063-ANSI V1 EN
(Equation 161)
The function has two stages that can be set independently.
With the parameter
OpMode1(2)
the function can be set
Enabled
/
Disabled
.
The function gives trip if the power component in the direction defined by the setting
Angle1(2)
is smaller than the set pick up power value
Power1(2)
1MRK 506 334-UUS A
Section 7
Current protection
249
Application manual