VDiffSC
Setting for voltage difference between line and bus in p.u. This setting in p.u is defined as
(measured V-Bus/VBase for bus according to
GblBaseSelBus
) - (measured V-Line/VBase
for line according to
GblBaseSelLine
). A typical value for the voltage difference can be
15%.
FreqDiffM
and
FreqDiffA
The frequency difference level settings,
FreqDiffM
and
FreqDiffA
, shall be chosen
depending on the condition in the network. At steady conditions a low frequency
difference setting is needed, where the
FreqDiffM
setting is used. For auto-reclosing a
bigger frequency difference setting is preferable, where the
FreqDiffA
setting is used. A
typical value for the
FreqDiffM
can
10
mHz and a typical value for the
FreqDiffA
can be
100-200
mHz, when the synchronizing function is not used.
PhaseDiffM
and
PhaseDiffA
The phase angle difference level settings,
PhaseDiffM
and
PhaseDiffA
, shall also be
chosen depending on conditions in the network. The phase angle setting must be chosen
to allow closing under maximum load. A typical maximum value in heavy-loaded
networks can be 45 degrees whereas in most networks the maximum occurring angle is
below 25 degrees. The setting of
PhaseDiffA
setting is limited by the
PhaseDiffM
setting.
tSCM
and
tSCA
The purpose of the timer delay settings,
tSCM
and
tSCA
, is to ensure that the synchronism
check conditions remains constant and that the situation is not due to a temporary
interference. Should the conditions not persist for the specified time, the delay timer is
reset and the procedure is restarted when the conditions are fulfilled again. Circuit breaker
closing is thus not permitted until the synchronism check situation has remained constant
throughout the set delay setting time. Under stable conditions a longer operation time
delay setting is needed, where the
tSCM
setting is used. During auto-reclosing a shorter
operation time delay setting is preferable, where the
tSCA
setting is used. A typical value
for the
tSCM
may be
1
second and a typical value for the
tSCA
may be
0.1
second.
Energizing check settings
AutoEnerg
and
ManEnerg
Two different settings can be used for automatic and manual closing of the circuit breaker.
The settings for each of them are:
•
Disabled
, the energizing function is disabled.
•
DLLB
, Dead Line Live Bus: the line voltage is below 40% of the line base voltage
UBase
according to the setting
GblBaseSelLine
about the Global Base Value group,
Section 11
1MRK 506 334-UUS A
Control
302
Application manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Страница 2: ......
Страница 30: ...24...
Страница 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Страница 110: ...104...
Страница 260: ...254...
Страница 274: ...268...
Страница 280: ...274...
Страница 396: ...390...
Страница 494: ...488...
Страница 506: ...500...
Страница 515: ...509...