In figure
and figure
the logic shows how a closing Lock-out logic can be designed
with the Lock-out relay as an external relay alternatively with the Lock-out created
internally with the Manual closing going through the Synchro-check function. Lock-out
arranged with an external Lock-out relay.
Lock-out
RXMD1
11
12
21
MAIN ZAK CLOSE
CLOSE COMMAND
SMBO
OR
STBRREC (79)
OR
CCRBRF (50BF)
BJ-TRIP
ZCVPSOF-TRIP
INHIBIT
UNSUCCL
TRBU
ANSI10000264-1-en.vsd
SET
RESET
ELECTRICAL RESET
RELAY
ANSI10000264 V1 EN
Figure 141:
Lock-out arranged with an external Lock-out relay
CLOSE COMMAND
OR
STBRREC (79)
OR
CSPBRF (50BF)
BJ-TRIP
ZCVPSOF-TRIP
INHIBIT
UNSUCCL
BJTRIP
ANSI10000265-1-en.vsd
STPPTRC (94)
SMBO
AND
RESET LOCK-OUT
OR
OR
SESRSYN (25)
SOFTWARE
OR IO RESET
AUTO STOP
MAN ENOK
MAN CLOSE
STBRREC (79) CLOSE
SETLKOUT
CLLOUT
RSTLOUT
ANSI10000265 V1 EN
Figure 142:
Lock-out arranged with internal logic with manual closing going through
in IED
11.3.2.18
Automatic continuation of the reclosing sequence
The auto-reclosing function can be programmed to proceed to the following reclosing
shots (if selected) even if the start signals are not received from the protection functions,
1MRK 506 334-UUS A
Section 11
Control
327
Application manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Страница 2: ......
Страница 30: ...24...
Страница 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Страница 110: ...104...
Страница 260: ...254...
Страница 274: ...268...
Страница 280: ...274...
Страница 396: ...390...
Страница 494: ...488...
Страница 506: ...500...
Страница 515: ...509...