Position evaluation POS_EVAL
•
Select release SELGGIO
•
Bay control QCBAY
•
Local remote LOCREM
•
Local remote control LOCREMCTRL
SCSWI, SXCBR, QCBAY and SXSWI are logical nodes according to IEC 61850. The
signal flow between these function blocks appears in figure
. The function Logical
node Interlocking (SCILO) in the figure
is the logical node for interlocking.
Control operation can be performed from the local IED HMI. If the administrator has
defined users with the UMT tool, then the local/remote switch is under authority control.
If not, the default (factory) user is the SuperUser that can perform control operations from
the local IED HMI without LogOn. The default position of the local/remote switch is on
remote.
SXCBR
SCSWI
SCILO
(3)
SCSWI
SCILO
(3)
SXSWI
-BKR1
-189
-989
IEC 61850
QCBAY
ANSI10000198_2_en.vsd
52
ANSI10000198 V2 EN
Figure 145:
Signal flow between apparatus control function blocks
1MRK 506 334-UUS A
Section 11
Control
337
Application manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Страница 2: ......
Страница 30: ...24...
Страница 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Страница 110: ...104...
Страница 260: ...254...
Страница 274: ...268...
Страница 280: ...274...
Страница 396: ...390...
Страница 494: ...488...
Страница 506: ...500...
Страница 515: ...509...