2
min
V
Zload
S
=
EQUATION1753-ANSI V1 EN
(Equation 69)
Where:
V
is the minimum phase-to-phase voltage in kV
S
is the maximum apparent power in MVA.
The load angle
LdAngle
can be derived according to equation
:
max
cos
max
P
LdAngle a
S
æ
ö
=
ç
÷
è
ø
EQUATION1623-ANSI V1 EN
(Equation 70)
where:
Pmax
is the maximal active power transfer during emergency conditions and
Smax
is the maximal apparent power transfer during emergency conditions.
The
RLd
can be calculated according to equation
:
cos(
)
RLd
ZLoad
LdAngle
=
×
EQUATION1624-ANSI V1 EN
(Equation 71)
The setting of
RLd
and
LdAngle
is by default set to 80 ohm/phase and 20 degrees. Those
values must be adapted to the specific application.
6.4
Additional distance protection directional function for
ground faults ZDARDIR (21D)
6.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Additional distance protection
directional function for ground faults
ZDARDIR
S00346 V1 EN
21D
1MRK 506 334-UUS A
Section 6
Impedance protection
149
Application manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Страница 2: ......
Страница 30: ...24...
Страница 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Страница 110: ...104...
Страница 260: ...254...
Страница 274: ...268...
Страница 280: ...274...
Страница 396: ...390...
Страница 494: ...488...
Страница 506: ...500...
Страница 515: ...509...