(controlled by the PSTO input), giving switching commands through the CMDPOS12 and
CMDPOS21 outputs.
The output POSITION is an integer output, showing the actual position as an integer
number 0 – 3.
An example where VSGGIO is configured to switch Autorecloser enabled–disabled from
a button symbol on the local HMI is shown in
. The Close and Open buttons on
the local HMI are normally used for enable–disable operations of the circuit breaker.
IEC07000112-2-en_ansi.vsd
PSTO
CMDPOS12
IPOS1
NAM_POS1
NAM_POS2
IPOS2
CMDPOS21
Disabled
Enabled
VSGGIO
SMBRREC_79
ON
OFF
SETON
INTONE
INV
OUT
INPUT
ANSI07000112 V2 EN
Figure 190:
Control of Autorecloser from local HMI through Selector mini switch
11.7.3
Setting guidelines
Selector mini switch (VSGGIO) function can generate pulsed or steady commands (by
setting the
Mode
parameter). When pulsed commands are generated, the length of the
pulse can be set using the
tPulse
parameter. Also, being accessible on the single line
diagram (SLD), this function block has two control modes (settable through
CtlModel
):
Dir Norm
and
SBO Enh
.
11.8
IEC61850 generic communication I/O functions
DPGGIO
11.8.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IEC 61850 generic communication I/O
functions
DPGGIO
-
-
1MRK 506 334-UUS A
Section 11
Control
387
Application manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Страница 2: ......
Страница 30: ...24...
Страница 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Страница 110: ...104...
Страница 260: ...254...
Страница 274: ...268...
Страница 280: ...274...
Страница 396: ...390...
Страница 494: ...488...
Страница 506: ...500...
Страница 515: ...509...