Enabled: It is recommended to have the function activated in the application
•
Disabled: It is recommended to have the function deactivated in the application
•
Application dependent: The decision to have the function activated or not is
dependent on the specific conditions in each case
Application 1- 5 in table
are according to application examples given in
previous sections.
Table 1:
Selection of functions in different applications
Function
Application 1
Application 2
Application 3
Application 4
Application 5
Five zone distance protection, quadrilateral
characteristic ZQMPDIS (21)
Enabled
Enabled
Enabled
Enabled
Enabled
Phase selection with load enchroachment,
quadrilateral characteristic FDPSPDIS (21)
Enabled
Enabled
Enabled
Enabled
Enabled
Faulty phase identification with load enchroachment
for mho FMPSPDIS
Enabled
Enabled
Enabled
Enabled
Enabled
Local acceleration logic ZCLCPLAL
Application
dependent
Application
dependent
Application
dependent
Application
dependent
Application
dependent
Phase preference logic PPLPHIZ
Disabled
Disabled
Disabled
Disabled
Enabled
Power swing detection ZMRPSB (68)
Application
dependent
Application
dependent
Application
dependent
Disabled
Application
dependent
Automatic switch onto fault logic, voltage and current
based ZCVPSOF
Enabled
Enabled
Enabled
Enabled
Enabled
Instantaneous phase overcurrent protection, 3-phase
output PHPIOC (50)
Application
dependent
Application
dependent
Application
dependent
Application
dependent
Application
dependent
Four step phase overcurrent protection, 3-phase
output OC4PTOC (51_67)
Enabled
Enabled
Enabled
Enabled
Enabled
Instantaneous residual overcurrent protection EFPIOC
(50N)
Enabled
Enabled
Enabled
Enabled
Disabled
Four step residual overcurrent protection EF4PTOC
(51N_67N)
Enabled
Enabled
Enabled
Enabled
Disabled
Scheme communication logic with delta based
blocking scheme signal transmit ZCPSCH(85)
Application
dependent
Enabled
Enabled
Disabled
Application
dependent
Current reversal and WEI logic for distance protection,
3-phase ZCRWPSCH (85)
Application
dependent
Enabled
Enabled
Disabled
Application
dependent
Scheme communication logic for residual overcurrent
protection ECPSCH (85)
Application
dependent
Enabled
Enabled
Disabled
Disabled
Current reversal and weak-end infeed logic for residual
overcurrent protection ECRWPSCH (85)
Application
dependent
Application
dependent
Enabled
Disabled
Disabled
Sensitive directional residual over current and power
protection SDEPSDE (67N)
Disabled
Disabled
Disabled
Disabled
Enabled
Thermal overload protection, one time constant
LFPTTR/LCPTTR (26) Fahrenheit/Celsius
Application
dependent
Enabled
Application
dependent
Application
dependent
Application
dependent
Table continues on next page
1MRK 506 334-UUS A
Section 2
Application
39
Application manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Страница 2: ......
Страница 30: ...24...
Страница 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Страница 110: ...104...
Страница 260: ...254...
Страница 274: ...268...
Страница 280: ...274...
Страница 396: ...390...
Страница 494: ...488...
Страница 506: ...500...
Страница 515: ...509...