5.1.4
Local HMI functionality
5.1.4.1
Protection and alarm indication
Protection indicators
The protection indicator LEDs are Normal, Pickup and Trip.
Table 3:
Normal LED (green)
LED state
Description
Off
Auxiliary supply voltage is disconnected.
On
Normal operation.
Flashing
Internal fault has occurred.
Table 4:
PickUp LED (yellow)
LED state
Description
Off
Normal operation.
On
A protection function has picked up and an indication message is displayed.
•
If several protection functions Pickup within a short time, the last Pickup is
indicated on the display.
Flashing
A flashing yellow LED has a higher priority than a steady yellow LED.
The IED is in test mode and protection functions are blocked.
•
The indication disappears when the IED is no longer in test mode and
blocking is removed.
Table 5:
Trip LED (red)
LED state
Description
Off
Normal operation.
On
A protection function has tripped and an indication message is displayed.
•
The trip indication is latching and must be reset via communication or by
pressing
.
Alarm indicators
The 15 programmable three-color LEDs are used for alarm indication. An individual
alarm/status signal, connected to any of the LED function blocks, can be assigned to one
of the three LED colors when configuring the IED.
Section 5
1MRK 506 334-UUS A
Local human-machine interface
110
Application manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Страница 2: ......
Страница 30: ...24...
Страница 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Страница 110: ...104...
Страница 260: ...254...
Страница 274: ...268...
Страница 280: ...274...
Страница 396: ...390...
Страница 494: ...488...
Страница 506: ...500...
Страница 515: ...509...