parameter the operation time of the step can never be shorter than the setting. Setting
range: 0.000 - 60.000s in steps of 0.001s.
IEC09000164-2
Operate time
Current
tx
tnMin
IMinn
IEC09000164 V2 EN
Figure 87:
Minimum operate current and operation time for inverse time
characteristics
In order to fully comply with curves definition setting parameter
tnMin
shall be set to the
value, which is equal to the operating time of the selected inverse curve for measured
current of twenty times the set current pickup value. Note that the operating time value is
dependent on the selected setting value for time multiplier
TDn
.
HarmRestrainx
: Enable block of step
n
from the harmonic restrain function (2nd
harmonic). This function should be used when there is a risk if power transformer inrush
currents might cause unwanted trip. Can be set
Disabled
/
Enabled
.
7.3.3.2
2nd harmonic restrain
If a power transformer is energized there is a risk that the transformer core will saturate
during part of the period, resulting in an inrush transformer current. This will give a
declining residual current in the network, as the inrush current is deviating between the
phases. There is a risk that the phase overcurrent function will give an unwanted trip. The
inrush current has a relatively large ratio of 2
nd
harmonic component. This component can
be used to create a restrain signal to prevent this unwanted function.
The settings for the 2nd harmonic restrain are described below.
1MRK 506 334-UUS A
Section 7
Current protection
183
Application manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Страница 2: ......
Страница 30: ...24...
Страница 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Страница 110: ...104...
Страница 260: ...254...
Страница 274: ...268...
Страница 280: ...274...
Страница 396: ...390...
Страница 494: ...488...
Страница 506: ...500...
Страница 515: ...509...