Table 17:
Voltage settings examples
Line voltage
Bus voltage
Bus voltage pre-
processing
SESRSYN setting
PhaseShift
URatio
UL1
UL1
Connect UL1 to
channel 1
-
1
UL2
Connect UL2 to
channel 1
- 120º
1
UL3
Connect UL3 to
channel 1
+ 120º
1
UL1L2
UL1L2
Connect UL1L2
to channel 1
-
1
UL2L3
Connect UL2L3
to channel 1
- 120º
1
UL3L1
Connect UL3L1
to channel 1
+ 120º
1
UL1
UL1L2
Connect UL1L2
to channel 1
- 30º
1.73
UL2L3
Connect UL2L3
to channel 1
- 90º
1.73
UL3L1
Connect UL3L1
to channel 1
+150º
1.73
Synchronizing settings
OperationSynch
The setting
Disabled
disables the Synchronizing function. With the setting
Enabled
, the
function is in service and the output signal depends on the input conditions.
FreqDiffMin
The setting
FreqDiffMin
is the minimum frequency difference where the system are
defined to be asynchronous. For frequency difference lower than this value the systems
are considered to be in parallel. A typical value for the
FreqDiffMin
is
10
mHz. Generally,
the value should be low if both, synchronizing and synchrocheck function is provided as
it is better to let synchronizing function close as it will close at the exact right instance if
the networks run with a frequency difference.
Note! The
FreqDiffMin
shall be set to the same value as
FreqDiffM
respective
FreqDiffA
for SESRSYN (25)irrespective of whether the
functions are used for manual operation, autoreclosing or both.
FreqDiffMax
Section 11
1MRK 506 334-UUS A
Control
300
Application manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Страница 2: ......
Страница 30: ...24...
Страница 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Страница 110: ...104...
Страница 260: ...254...
Страница 274: ...268...
Страница 280: ...274...
Страница 396: ...390...
Страница 494: ...488...
Страница 506: ...500...
Страница 515: ...509...