Power line carrier (PLC)
•
Microwave link (radio)
•
Optic fibre link
There are the following alternatives for communication scheme:
•
Under-reach permissive logic
•
Over-reach permissive logic
•
Blocking scheme
1.
Set
SchemeType
to
Permissive OR
This corresponds to over-reach permissive scheme. The choice is based on the
following:
Permissive over-reach scheme is chosen because it is considered as the weak end
infeed logic shall be used as there is a risk of small current infeed. Th WEI function
requires permissive over-reach communication scheme.
2.
Set
tCoord
to
0.000 s
3.
Set
tSendMin
to
0.100 s
3.1.11.1
Over-reach permissive logic
The principle of the logic can be explained as shown in figure
.
Z 1 = R 1 + jX 1
Z 0 = R 0 + jX0
A
B
Step 1- reach
C
Communication
Step 2- reach
Step 1- reach
Step 2- reach
Y
Y
REL 650
REL 650
ANSI11000115_2_en.vsd
ANSI11000115 V2 EN
Figure 25:
Principle for four step residual overcurrent protection overreach
communication scheme
1MRK 506 334-UUS A
Section 3
REL650 setting examples
75
Application manual