Intertrip scheme
•
Permissive underreaching scheme
•
Permissive overreaching scheme
•
Blocking scheme
•
Delta blocking scheme
As an example the setting guidelines for delta blocking scheme is given below:
Delta blocking scheme
1.
Set
Operation
=
Enabled
2.
Set
SchemeType
=
DeltaBlocking
3.
Set
tCoord
=
0.000 s
4.
Set
tSendMin
=
0.000 s
5.
Set
Unblock
=
Disabled
(Set to
NoRestart
if Unblocking scheme with no alarm for loss of guard is to be used.
Set to
Restart
if Unblocking scheme with alarm for loss of guard is to be used.)
6.
Set
tSecurity
=
0.035 s
7.
Set
DeltaI
=
10 %IB
8.
Set
DeltaV
=
5 %VB
9.
Set
Delta3I0
=
10 %IB
10. Set
Delta3V0
=
5 %VB
3.1.6.1
Principles for over-reach permissive communication logic
The principle of the logic can be explained as shown in figure
Z 1 = R 1 + jX 1
Z 0 = R 0 + jX0
A
B
Zone 1
Zone 2
C
Zone 1
Zone 2
Communication
Y
Y
REL 650
REL 650
ANSI11000111_1_en.vsd
ANSI11000111 V1 EN
Figure 12:
Principle of over-reach communication scheme
Section 3
1MRK 506 334-UUS A
REL650 setting examples
58
Application manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Страница 2: ......
Страница 30: ...24...
Страница 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Страница 110: ...104...
Страница 260: ...254...
Страница 274: ...268...
Страница 280: ...274...
Страница 396: ...390...
Страница 494: ...488...
Страница 506: ...500...
Страница 515: ...509...