Transformer
protection
Transformer
Line
Line
Setting of current input:
Set parameter
CT_WyePoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Forward
Reverse
Definition of direction for
directional functions
Line protection
Setting of current input:
Set parameter
CT_WyePoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Setting of current input:
Set parameter
CT_WyePoint with
Line as
reference object.
Correct setting is
"ToObject"
ANSI11000020-2-en.vsd
I
s
I
s
I
p
I
p
I
p
IED
IED
ANSI11000020 V2 EN
Figure 36:
Example how to set CT_WyePoint parameters in the IED
The figure
shows the most common case where the objects have their own CTs. For the
transformer protection, the protected object is the transformer. Therefore both
CT_WyePoint
directions should be set
ToObject
. For the line protection, the protected
object is the line. The line CT is grounded towards the busbar, therefore the
CT_WyePoint
should be set
FromObject
.
4.2.3.2
Example 2
Two IEDs used for protection of two objects and sharing a CT.
Section 4
1MRK 506 334-UUS A
Analog inputs
92
Application manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Страница 2: ......
Страница 30: ...24...
Страница 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Страница 110: ...104...
Страница 260: ...254...
Страница 274: ...268...
Страница 280: ...274...
Страница 396: ...390...
Страница 494: ...488...
Страница 506: ...500...
Страница 515: ...509...