3.1.3.1
Calculating general settings
1.
Set
GlobalBaseSel
to
1
2.
Set
LineAng
to
81.9º
The positive sequence impedance line angle for the protected line is calculated as
°
=
÷
ø
ö
ç
è
æ
=
÷÷
ø
ö
çç
è
æ
=
9
.
81
5
.
2
5
.
17
arctan
arctan
line
line
R
X
LineAng
GUID-A8BDC47F-A097-42F4-9C1F-DA6AB2D6AC1A V1 EN
(Equation 1)
3.
Set
CharPGZx
and
CharPPZx
to
Mho
,
Quadrilateral
and
Combined
as per the
application for each zone.
4.
Set KN-factors
4.1. Set
KNMag1
to
0.62
for Zone 1
4.2. Set
KNAng1
to
-0.6º
for Zone 1
4.3. Set
KNMag2
to
0.62
For Zones 2, 3, 4, 5
4.4. Set
KNAng2
to
-0.6º
for Zones 2,3,4 and 5
the KN-factor is calculated for correct reach for phase-to-ground faults . The
definition of the KN-factor is:
line
line
line
Z
Z
Z
KN
,
1
,
1
,
0
3
×
-
=
GUID-201DAAE3-7D9E-48B9-9CCA-33B5C2E51103 V1 EN
(Equation 2)
For phase-to-ground fault loops the apparent impedance is defined as:
,
,
0
3
ph Ln
ph ea
ph Ln
V
Z
I
KN
I
-
=
+
× ×
GUID-509FDDAF-4B92-4DD5-A9A9-B2214B58E383-ANSI V1 EN
(Equation 3)
The magnitude and phase angle are set separately as KN is a complex value. The
KN-factor can be set separately for zone 1 and for the other zones. This is mainly for
application for double circuit lines where zone 1 should be set to assure underreach
and the other zones should be set to assure overreach. For a single circuit line it is
recommended to set the KN-factors to the same values.
Let Z
1,line
= 2.5 + j17.5 and Z
0,line
= 7.5 + j17.5, then KN is calculated as:
Section 3
1MRK 506 334-UUS A
REL650 setting examples
46
Application manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Страница 2: ......
Страница 30: ...24...
Страница 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Страница 110: ...104...
Страница 260: ...254...
Страница 274: ...268...
Страница 280: ...274...
Страница 396: ...390...
Страница 494: ...488...
Страница 506: ...500...
Страница 515: ...509...