216 Parameters
No action
No action taken.
0
Warning only
Drive generates warning
the motor is overloaded to the warning level, that is,
reaches value 88.0%.
1
Warning and fault
Drive generates warning
the motor is overloaded to the warning level, that is,
reaches value 88.0%.
when the
motor is overloaded to the fault level, that is,
reaches value 100.0%.
2
Defines the motor overload class to be used. The
class of
protection is specified by the user as the time for
tripping at 6 times the tripping level current.
The function shares the following parameters with
the Motor thermal model:
•
•
•
Together, these three parameters set the tripping
level as a function of motor frequency.
Class 20
Class 5
Motor overload class 5.
0
Class 10
Motor overload class 10.
1
Class 20
Motor overload class 20.
2
Class 30
Motor overload class 30.
3
Class 40
Motor overload class 40.
4
36
Peak value and amplitude logger settings.
See also section
Selects the signal to be monitored by the peak value
logger.
The signal is filtered using the filtering time specified
by parameter
The peak value is stored, along with other pre-
selected signals at the time, into parameters
…
.
The peak value logger can be reset using parameter
. The date and time of the last
reset are stored into parameters
and
respectively.
not used
None (peak value logger disabled).
0
Motor speed used
1
Output frequency
.
3
Motor current
.
4
Motor torque
.
6
DC voltage
7
Output power
. 8
Speed ref ramp in
10
No.
Name/Value
Description
Default
FbEq 16
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...