60 Program features
The graph below shows the PID trim output in direct mode throughout the
speed range. A fixed trim speed reference is added throughout the speed range.
Note:
In the above graph, it is assumed that the PID output is limited or stable
at 100. This is for clarity only. In real life scenarios, the PID output can vary based
on the setpoint and the actual value.
Example
:
If:
parameter
= Speed
parameter
parameter
= 1500 rpm
parameter
= 100 (limited to 100)
parameter
= 0.5,
then:
Proportional
The proportional method is suitable for applications where tension control is
required throughout the speed range but not near zero speed.
In this mode, the PID trim output actual (parameter
) is relative to the reference selected by parameter
It is recommended that the speed reference selected in
and the reference source in
are equal. This is
required to make the proportional mode active.
In most of the use cases, the process speed reference is connected in
. For example, if EXT1 control mode is used and the
Drive speed reference
0
Par40.05
100
100
----------
1500
0.5
=
Par40.05
750
=