130 Parameters
In1P Start; In2 Stop
The sources of the start and stop commands are
selected by parameters
. The state transitions of the
source bits are interpreted as follows:
Notes:
• Parameter
has no
effect with this setting.
• When source 2 is 0, the Start and Stop keys on the
control panel are disabled.
4
In1P Start; In2 Stop; In3
Dir
The sources of the start and stop commands are
selected by parameters
. The source selected by
determines the direction. The state
transitions of the source bits are interpreted as
follows:
Notes:
• Parameter
has no
effect with this setting.
• When source 2 is 0, the Start and Stop keys on the
control panel are disabled.
5
In1P Start fwd; In2P
Start rev; In3 Stop
The sources of the start and stop commands are
selected by parameters
and
. The source
determines the
direction. The state transitions of the source bits are
interpreted as follows:
Note:
Parameter
effect with this setting.
6
Control panel
Start; stop and direction commands through control
panel; when EXT1 is active. Applies also for PC-Tool
when it is connected via panel port.
11
No.
Name/Value
Description
Default
FbEq 16
State of source 1
(
)
State of source 2
Command
0 -> 1
1
Start
Any
0
Stop
State of
source 1
(
State of
source 2
State of
source 3
Command
0 -> 1
1
0
Start forward
0 -> 1
1
1
Start reverse
Any
0
Any
Stop
State of
source 1
)
State of
source 2
(
)
State of
source 3
Command
0 -> 1
Any
1
Start forward
Any
0 -> 1
1
Start reverse
Any
Any
0
Stop
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...