72 Program features
When adaptive voltage limit is disabled in parameter
:
Settings and diagnostics
Parameters
),
(page
),
(page
) and
Events: -
DC voltage level [V]
95.01 Supply Voltage
See
AC supply
voltage range
[V]
208…240
AC supply
voltage range
[V]
380…415
AC supply
voltage range
[V]
440…480
Automatic /
not used
< 456AC
> 456AC
Overvoltage fault
limit
421
842
842
842
842
Overvoltage control
limit
389
779
779
779
779
Internal brake
chopper start limit
389
779
779
779
779
Internal brake
chopper start limit
379
759
759
759
759
Overvoltage warning
limit
372
745
745
745
745
Undervoltage
warning limit
0.85×1.35×208
= 239
0.85×1.35×380
= 436
0.85×1.35×440
= 505
0.85×1.35×380
= 436
0.85×1.35×440
= 505
Undervoltage
control limit
0.78×1.35×208
= 219
0.78×1.35×380
= 400
0.78×1.35×440
= 463
0.78×1.35×180
= 400
0.78×1.35×440
= 463
Charging relay
closing limit
0.78×1.35×208
= 219
0.78×1.35×380
= 400
0.78×1.35×440
= 463
0.78×1.35×180
= 400
0.78×1.35×440
= 463
Charging relay
opening limit
0.73×1.35×208
= 205
0.73×1.35×380
= 374
0.73×1.35×440
= 434
0.73×1.35×380
= 374
0.73×1.35×440
= 434
DC voltage at upper
bound of supply
voltage range
(
U
DCmax
)
324
560
648
(variable)
(variable)
DC voltage at lower
bound of supply
voltage range
(
U
DCmin
)
281
513
594
(variable)
(variable)
Charging
activation/standby
limit
0.73×1.35×
208
= 205
0.73×1.35×
380
= 374
0.73×1.35×
440
= 434
0.73×1.35×
380
= 374
0.73×1.35×
440
= 434
Undervoltage fault
limit
0.73×1.35×
208
= 205
0.73×1.35×
380
= 374
0.73×1.35×
440
= 434
0.73×1.35×
380
= 374
0.73×1.35×
440
= 434
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...