Parameters 139
Defines the delay for the zero speed delay function.
The function is useful in applications where a smooth
and quick restarting is essential. During the delay, the
drive knows the rotor position accurately.
0 ms
Without zero speed delay:
The drive receives a stop command and decelerates
along a ramp. When actual motor speed falls below
the value of parameter
, inverter
modulation is stopped and the motor coasts to a
standstill.
With zero speed delay:
The drive receives a stop command and decelerates
along a ramp. When actual motor speed falls below
the value of parameter
, the
zero speed delay function activates. During the delay
the function keeps the speed controller live: the
inverter modulates, motor is magnetized and the
drive is ready for a quick restart. Zero speed delay can
be used e.g. with the jogging function.
0…30000 ms
Zero speed delay.
1 = 1 ms
No.
Name/Value
Description
Default
FbEq 16
Speed controller switched
off: Motor coasts to a stop.
Speed
Time
Speed controller remains
active. Motor is decelerated
to true zero speed.
Speed
Time
Delay