Parameters 125
Supervision 4
.
28
Supervision 5
Bit 4 of
29
Supervision 6
Bit 5 of
.
30
EFB MCW bit 11
Control word bit 11 received through the embedded
fieldbus interface.
32
EFB connection loss
Detected communication loss of embedded fieldbus
interface changes control mode to EXT2.
35
-
Selects the operating mode for external control
location EXT1 in vector motor control mode.
Zero
None.
1
Speed
Speed control. The torque reference used is
Torque reference speed control
(output of the speed
reference chain).
2
Torque
Torque control. The torque reference used is
(output of the torque reference
chain).
3
Minimum
Combination of selections
and
: the
torque selector compares the speed controller output
Torque reference speed control
) and the
torque reference (
selects the smaller of the two.
If speed error becomes negative, the drive follows the
speed controller output until speed error becomes
positive again. This prevents the drive from
accelerating uncontrollably if the load is lost in torque
control.
4
Maximum
Combination of selections
and
: the
torque selector compares the speed controller output
Torque reference speed control
) and the
torque reference (
selects the greater of the two.
If speed error becomes positive, the drive follows the
speed controller output until speed error becomes
negative again. This prevents the drive from
accelerating uncontrollably if the load is lost in torque
control.
5
Selects the operating mode for external control
location EXT2 in vector motor control mode.
For the selections, see parameter
.
Selects the operating mode for local control in vector
motor control mode.
Speed
Speed control. The torque reference used is
Torque reference speed control
(output of the speed
reference chain).
0
Torque
Torque control. The torque reference used is
(output of the torque reference
chain).
1
No.
Name/Value
Description
Default
FbEq 16
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...