Parameters 179
Defines the shape of the acceleration and
deceleration ramps used with the set 1.
0.000 s: Linear ramp. Suitable for steady acceleration
or deceleration and for slow ramps.
0.001…1000.000 s: S-curve ramp. S-curve ramps are
ideal for lifting applications. The S-curve consists of
symmetrical curves at both ends of the ramp and a
linear part in between.
Acceleration:
Deceleration:
0.000 s
0.000…1800.000 s
Ramp shape at start and end of acceleration and
deceleration.
10 = 1 s
Defines the shape of the acceleration and
deceleration ramps used with the set 2. See
parameter
.
0.000 s
0.000…1800.000 s
Ramp shape at start and end of acceleration and
deceleration.
10 = 1 s
No.
Name/Value
Description
Default
FbEq 16
S-curve ramp:
> 0 s
Linear ramp:
= 0 s
Linear ramp:
= 0 s
S-curve ramp:
> 0 s
Speed
Time
S-curve ramp:
Linear ramp:
= 0 s
S-curve ramp:
> 0 s
Speed
Time
Linear ramp:
= 0 s
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...