206 Parameters
Defines the hysteresis for the signal monitored by
signal supervision 4.
Note
: This parameter applies to all selections of
, not just Hysteresis.
0.00
0.00…100000.00
Hysteresis.
-
Selects the mode of signal supervision function 5.
Determines how the monitored signal (see parameter
) is compared to its lower and upper limits (
and
respectively). The action to be taken when
the condition is fulfilled is selected by
.
Disabled
Signal supervision 5 not in use.
0
Low
Action is taken whenever the signal is below the
Supervision 1 low limit - 0.5 * hysteresis.
Action is deactivated whenever the signal is above
the Supervision 1 low limit + 0.5 * hysteresis.
1
High
Action is taken whenever the signal is above the
Supervision 1 high limit + 0.5 * hysteresis.
Action is deactivated whenever the signal is below
the Supervision 1 high limit - 0.5 * hysteresis.
2
Abs low
Action is taken whenever the absolute value of the
signal is below the absolute value of the Supervision 1
low limit - 0.5 * hysteresis.
Action is deactivated whenever the absolute value
of the signal is above the absolute value of the
Supervision 1 low limit + 0.5 * hysteresis.
3
Abs high
Action is taken whenever the absolute value of the
signal is above the absolute value of the Supervision 1
high limit + 0.5 * hysteresis.
Action is deactivated whenever the absolute value
of the signal is below the absolute value of the
Supervision 1 high limit - 0.5 * hysteresis.
4
Both
Action is taken whenever the signal is above the
Supervision 1 high limit + 0.5 * hysteresis or below
the Supervision 1 low limit - 0.5*hysteresis.
Action is deactivated whenever the signal is in
between the Supervision 1 high limit - 0.5 * hysteresis
and the Supervision 1 low limit + 0.5 * hysteresis.
5
Abs both
Action is taken whenever the absolute value of the
signal is above the absolute value of the Supervision 1
high limit + 0.5 * hysteresis or below the absolute
value of the Supervision 1 low limit - 0.5 * hysteresis.
Action is deactivated whenever the absolute value
of the signal is in between the absolute value of the
Supervision 1 high limit - 0.5 * hysteresis and the
absolute value of the Supervision 1 low limit + 0.5 *
hysteresis.
6
No.
Name/Value
Description
Default
FbEq 16
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...