Parameters 205
Hysteresis
Action is taken whenever the signal is above the
Supervision 1 high limit + 0.5 * hysteresis.
Action is deactivated whenever the signal is below
the Supervision 1 low limit - 0.5 * hysteresis.
The status is unchanged when the signal value is
in between the Supervision 1 high limit + 0.5 *
hysteresis and the Supervision 1 low limit - 0.5 *
hysteresis.
7
Low falling
Action is taken whenever the signal falls from a value
higher than the Supervision 1 low limit + 0.5 *
hysteresis to a value which is lower than the
Supervision 1 low limit - 0.5 * hysteresis.
Action is deactivated when the signal rises to higher
than the Supervision 1 low limit + 0.5*hysteresis.
Note:
Supervision action is also deactivated for every
motor start command.
8
High rising
Action taken whenever the signal rises from a value
lower than the Supervision 1 high limit - 0.5 *
hysteresis to a value which is higher than the
Supervision 1 high limit + 0.5 * hysteresis.
Action is deactivated when the signal falls to lower
than the Supervision 1 high limit - 0.5 * hysteresis.
Note:
Supervision action is also deactivated for every
motor start command.
9
Selects whether the drive generates a fault, warning
or neither when the value monitored by signal
supervision 4 exceeds its limits.
Note:
This parameter does not affect the status
indicated by
No action
No warning or fault generated.
0
Warning
Warning
is generated.
1
Fault
The drive trips on fault
.
2
Fault if running
The drive trips on fault
if
running.
3
Selects the signal to be monitored by signal
supervision function 4.
For the available selections, see parameter
.
Defines a filter time constant for the signal monitored
by signal supervision 4.
0.000 s
0.000 … 30.000 s
Signal filter time.
1000 = 1 s
Defines the lower limit for signal supervision 4.
0.00
-21474830.00…
21474830.00
Low limit.
-
Defines the upper limit for signal supervision 4.
0.00
-21474830.00…
21474830.00
Upper limit.
-
No.
Name/Value
Description
Default
FbEq 16
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...