Parameters 197
32
Configuration of signal supervision functions 1…3.
Three values can be chosen to be monitored; a
warning or fault is generated whenever predefined
limits are exceeded.
See also section
(page
Signal supervision status word.
Indicates whether the values monitored by the signal
supervision functions are within or outside their
respective limits.
Note:
This word is independent of the drive actions
defined by parameters
and
0000h
0000h...FFFFh
Signal supervision status word.
1 = 1
Selects the mode of signal supervision function 1.
Determines how the monitored signal (see parameter
) is compared to its lower and upper limits
respectively). The action to be taken
when the condition is fulfilled is selected by
Disabled
Signal supervision 1 not in use.
0
Low
Action is taken whenever the signal is below the
Supervision 1 low limit - 0.5 * hysteresis.
Action is deactivated whenever the signal is above
the Supervision 1 low limit + 0.5 * hysteresis.
1
High
Action is taken whenever the signal is above the
Supervision 1 high limit + 0.5 * hysteresis.
Action is deactivated whenever the signal is below
the Supervision 1 high limit - 0.5 * hysteresis.
2
Abs low
Action is taken whenever the absolute value of the
signal is below the absolute value of the Supervision 1
low limit - 0.5 * hysteresis.
Action is deactivated whenever the absolute value
of the signal is above the absolute value of the
Supervision 1 low limit + 0.5 * hysteresis.
3
Abs high
Action is taken whenever the absolute value of the
signal is above the absolute value of the Supervision 1
high limit + 0.5 * hysteresis.
Action is deactivated whenever the absolute value
of the signal is below the absolute value of the
Supervision 1 high limit - 0.5 * hysteresis.
4
No.
Name/Value
Description
Default
FbEq 16
Bit
Name
Description
0
Supervision 1 active
is outside its limits.
1
Supervision 2 active
is outside its limits.
2
Supervision 3 active
is outside its limits.
3
Supervision 4 active
is outside its limits.
4
Supervision 5 active
is outside its limits.
5
Supervision 6 active
is outside its limits.
6…15
Reserved
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...