222 Parameters
Defines the fifth speed point.
See parameter
1800.0 rpm
-30000.0…30000.0
rpm
Speed.
1 = 1 rpm
Defines the first of the five frequency points on the X-
axis of the user load curve.
The values of the parameters must satisfy: -500.0 Hz
<
37.16 ULC frequency table point 1
<
37.19 ULC frequency table point 4
<
< 500.0 Hz.
Frequency points are used if parameter
is set to
and the reference unit is
Hz.
The five points must be in order from lowest to
highest. The points are defined as positive values, but
the range is
symmetrically effective also in the negative direction.
The
monitoring is not active outside these two areas.
5.0 Hz
-598.00…598.00 Hz
Frequency.
1 = 1 Hz
Defines the second frequency point.
See parameter
37.16 ULC frequency table point 1
.
25.0 Hz
-598.00…598.00 Hz
Frequency.
1 = 1 Hz
Defines the third frequency point.
See parameter
37.16 ULC frequency table point 1
.
43.0 Hz
-598.00…598.00 Hz
Frequency.
1 = 1 Hz
Defines the fourth frequency point.
See parameter
37.16 ULC frequency table point 1
.
50.0 Hz
-598.00…598.00 Hz
Frequency.
1 = 1 Hz
Defines the fifth frequency point.
See parameter
37.16 ULC frequency table point 1
.
60.0 Hz
-598.00…598.00 Hz
Frequency.
1 = 1 Hz
Defines the first of the five points on the Y-axis that
together with the corresponding point on the X-axis
or
…
) define the underload
(lower) curve.
The following conditions must be fulfilled:
•
•
•
•
•
10.0%
-1600.0…1600.0%
Underload point.
1 = 1%
No.
Name/Value
Description
Default
FbEq 16
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...