Fieldbus control through the embedded fieldbus interface (EFB)
409
6046h 0
Number of
Entries
U8
RO
The values shall be given in rotations
per minute (rpm) or in user-defined
velocity unit if the Vl Dimension Factor
object is not set to 1.
1
VI Velocity
Min Amount
U32
RWW
Always zero.
2
VI Velocity
Max Amount
U32
RWW
Mapped internally to the Vl Velocity Max
Pos and Vl Velocity Max Neg values.
6048h 0
Number of
Entries
U8
RO
This object indicates the configured
delta speed and delta time of the slope
of the acceleration ramp:
Vl Velocity Acceleration = Delta Speed
/ Delta Time
1
Delta Speed
U32
RWW
The value shall be given in rotations per
minute (rpm) or in user-defined velocity
unit if the Vl Dimension Factor object is
not set to 1.
2
Delta Time
U6
RWW
Value shall be given in seconds.
6049h 0
Number of
Entries
U8
RO
This object indicates the configured
delta speed and delta time of the slope
of the deceleration ramp:
Vl Velocity Deceleration = Delta Speed
/ Delta Time
1
Delta Speed
U32
RWW
The value shall be given in rotations per
minute (rpm) or in user-defined velocity
unit if the Vl Dimension Factor object is
not set to 1.
2
Delta Time
U6
RWW
Value shall be given in seconds.
604C
h
0
Highest sub-
index
supported
U8
Const
This object indicates the configured
numerator and denominator of the Vl
Dimension Factor. The Vl Dimension
Factor serves to include gearing in
calculation or serves to scale the
frequencies or specific units of the
user. It influences the Vl Target
Velocity, Vl Velocity Demand, Vl Velocity
Actual Value as well as the velocity limit
function and the ramp function.
1
VI Dimension
Factor
Numerator
INT32 RW
Multiplier for VI velocity values. Shall
not be 0.
2
VI Dimension
Factor
Denominator
INT32 RW
Divider for VI velocity values. Shall not
be 0.
Index
Sub-
inde
x
Name
Type
Access Description
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...