268 Parameters
0...255
Transmission type.
0 = acyclic synchronous
1...240 = cyclic synchronous
252 = synchronous RTR only
253 = asynchronous RTR only
254…255 = asynchronous
1=1
Set the event timer of the PDO.
Changing this parameter has an effect only if
58.23
Configuration location
is
Drive parameters
and after
the control unit is rebooted or the new settings
validated by parameter
Note
: If parameter
= [1] Modbus RTU, this
parameter is hidden.
0
0...65535
Event timer
0 = no timeout
other = if this PDO is enabled and has not been
transmitted for event timer milliseconds, a
transmission is forced
1=1 ms
Defines the address in the drive which the Modbus
master accesses when it reads from or writes to the
register address corresponding to Modbus register 1
(400001).
The master defines the type of the data (input or
output). The value is transmitted in a Modbus frame
consisting of two 16-bit words. If the value is 16-bit, it
is transmitted in the LSW (least significant word). If
the value is 32-bit, the subsequent parameter is also
reserved for it and must be set to
None
.
None
No mapping, register is always zero.
0
CW 16bit
CiA402
and
Transparent 16 profiles: 16-bit
control word;
: lower 16 bits of the DCU
control word
1
Ref1 16bit
Reference REF1 (16 bits)
2
Ref2 16bit
Reference REF2 (16 bits)
3
SW 16bit
profile: 16-bit ABB drives status word;
: lower 16 bits of the DCU status word
4
Act1 16bit
Actual value ACT1 (16 bits)
5
Act2 16bit
Actual value ACT2 (16 bits)
6
CW 32bit
Control Word (32 bits)
11
Ref1 32bit
Reference REF1 (32 bits)
12
Ref2 32bit
Reference REF2 (32 bits)
13
SW 32bit
Status Word (32 bits)
14
Act1 32bit
Actual value ACT1 (32 bits)
15
Act2 32bit
Actual value ACT2 (32 bits)
16
CW2 16bit
: upper 16
bits of the DCU control word
21
SW2 16bit
profile: not used / always zero;
: upper 16 bits of the DCU status word.
24
No.
Name/Value
Description
Default
FbEq 16
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...