264 Parameters
0x0000...0x07ff
COB-ID.
0 = RPDO disabled, 1 = use COB-ID from CiA 301 pre-
defined connection set, <other value> = use selected
COB-ID.
1=1
Set the transmission type of the PDO.
Changing this parameter has an effect only if
58.23
Configuration location
is
Drive parameters
and after
the control unit is rebooted or the new settings
validated by parameter
).
Note
: If parameter
= [1] Modbus RTU, this
parameter is hidden.
255
0...255
Transmission type.
0 = acyclic synchronous
1...240 = cyclic synchronous
252 = synchronous RTR only
253 = asynchronous RTR only
254…255 = asynchronous
1=1
Set the event timer of the PDO.
Changing this parameter has an effect only if
58.23
Configuration location
is
Drive parameters
and after
the control unit is rebooted or the new settings
validated by parameter
Note
: If parameter
= [1] Modbus RTU, this
parameter is hidden.
0
0...65535
Defines the time-out time for the PDO.
0 = no timeout
other = if this PDO is enabled and not received for
event timer milliseconds,
is performed.
Note
: The timeout supervision is activated upon a
successful reception of the RPDO.
1=1 ms
Set the COB-ID of the PDO.
Changing this parameter has an effect only if
58.23
Configuration location
is
Drive parameters
and after
the control unit is rebooted or the new settings
validated by parameter
Note
: If parameter
= [1] Modbus RTU, this
parameter is hidden.
0x0001
0x0000...0x07ff
COB-ID.
0 = RPDO disabled, 1 = use COB-ID from CiA 301 pre-
defined connection set, <other value> = use selected
COB-ID.
1=1
Set the transmission type of the PDO.
Changing this parameter has an effect only if
58.23
Configuration location
is
Drive parameters
and after
the control unit is rebooted or the new settings
validated by parameter
Note
: If parameter
= [1] Modbus RTU, this
parameter is hidden.
255
No.
Name/Value
Description
Default
FbEq 16
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...