Fieldbus control through the embedded fieldbus interface (EFB)
399
Status Word for the Transparent 32 Profile
Status word of the Transparent 32 profile can be read from the object 2004h.
26...
31
Reserved
Bit
Name
Value
State/Description
0
READY
1
Drive is ready to receive the start command.
0
Drive is not ready.
1
ENABLED
1
External run enable signal is active.
0
External run enable signal is not active.
2
Reserved for
ENABLED_TO_R
OTATE
Not yet implemented.
3
RUNNING
1
Drive is modulating.
0
Drive is not modulating.
4
ZERO_SPEED
1
Drive is at zero speed.
0
Drive is not at zero speed.
5
ACCELERATING 1
Not yet implemented.
0
Not yet implemented.
6
DECELERATING 1
Not yet implemented.
0
Not yet implemented.
7
AT_SETPOINT
1
Drive is at setpoint.
0
Drive is not at setpoint.
8
LIMIT
1
Drive operation is limited.
0
Drive operation is not limited.
9
SUPERVISION
1
Actual value (speed, frequency or torque) is above a
limit. Limit is set with parameters 46.31…46.33
0
Actual value (speed, frequency or torque) is within
limits.
10
REVERSE_REF
1
Not yet implemented.
0
Not yet implemented.
11
REVERSE_ACT
1
Not yet implemented.
0
Not yet implemented.
12
PANEL_LOCAL
1
Panel/keypad (or PC tool) is in local control mode.
0
Panel/keypad (or PC tool) is not in local control mode.
13
FIELDBUS_LOC
AL
1
Fieldbus is in local control mode.
0
Fieldbus is not in local control mode.
Bit
Name
Value
State/Description
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...