156 Parameters
Defines acceleration time 1 as the time required for
the speed to change from zero to the speed defined
by parameter
not
to parameter
If the speed reference increases faster than the set
acceleration rate, the motor speed will follow the
acceleration rate.
If the speed reference increases slower than the set
acceleration rate, the motor speed will follow the
reference.
If the acceleration time is set too short, the drive will
automatically prolong the acceleration in order not to
exceed the drive torque limits.
3.000 s
0.000 …1800.000 s
Acceleration time 1.
10 = 1 s
Defines deceleration time 1 as the time required for
the speed to change from the speed defined by
(
not
from parameter
) to zero.
If the speed reference decreases slower than the set
deceleration rate, the motor speed will follow the
reference.
If the reference changes faster than the set
deceleration rate, the motor speed will follow the
deceleration rate.
If the deceleration rate is set too short, the drive will
automatically prolong the deceleration in order not to
exceed drive torque limits (or not to exceed a safe DC
link voltage). If there is any doubt about the
deceleration time being too short, ensure that DC
overvoltage control is on (parameter
).
Note:
If a short deceleration time is needed for a high
inertia application, the drive should be equipped with
braking equipment such as a brake chopper and
brake resistor.
3.000 s
0.000 …1800.000 s
Deceleration time 1.
10 = 1 s
Defines acceleration time 2. See parameter
.
60.000 s
0.000 …1800.000 s
Acceleration time 2.
10 = 1 s
Defines deceleration time 2. See parameter
60.000 s
0.000 …1800.000 s
Deceleration time 2.
10 = 1 s
Defines the acceleration time for the jogging function
ie. the time required for the speed to change from
zero to the speed value defined by parameter
.
See section
on page
.
60.000 s
0.000 …1800.000 s
Acceleration time for jogging.
10 = 1 s
Defines the deceleration time for the jogging function
ie. the time required for the speed to change from the
speed value defined by parameter
to zero.
See section
on page
.
60.000 s
0.000 …1800.000 s
Deceleration time for jogging.
10 = 1 s
No.
Name/Value
Description
Default
FbEq 16
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...