Fault tracing 341
2330
Earth leakage
Programmable fault:
Drive has detected load
unbalance typically due to
earth fault in motor or motor
cable.
Check there are no power factor
correction capacitors or surge
absorbers in motor cable.
Check for an earth fault in motor or
motor cables by measuring the
insulation resistances of motor and
motor cable.
Try running the motor in scalar control
mode if allowed. (See parameter
If no earth fault can be detected,
contact your local ABB representative.
2340
Short circuit
Short-circuit in motor
cable(s) or motor.
Aux code 0x0080 indicates
that the state feedback from
output phases does not
match the control signals.
Check motor and motor cable for
cabling errors.
Check there are no power factor
correction capacitors or surge
absorbers in motor cable.
Cycle the power to the drive.
2381
IGBT overload
Excessive IGBT junction to
case temperature. This fault
protects the IGBT(s) and can
be activated by a short
circuit in the motor cable.
Check motor cable.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive
power.
3130
Input phase loss
Intermediate circuit DC
voltage is oscillating due to
missing input power line
phase or blown fuse.
Check input power line fuses.
Check for loose power cable
connections.
Check for input power supply
imbalance.
3181
Cross connection
Programmable fault:
Incorrect input power and
motor cable connection (ie.
input power cable is
connected to drive motor
connection).
Check input power connections.
3210
DC link overvoltage
Excessive intermediate
circuit DC voltage.
Check that overvoltage control is on
Check that the supply voltage matches
the nominal input voltage of the drive.
Check the supply line for static or
transient overvoltage.
Check deceleration time.
Use coast-to-stop function (if
applicable).
Retrofit drive with brake chopper and
brake resistor.
Check that the brake resistor is
dimensioned properly and the
resistance is between acceptable
range for the drive.
3220
DC link undervoltage Intermediate circuit DC
voltage is not sufficient
because of a missing supply
phase, blown fuse or fault in
the rectifier bridge.
Check supply cabling, fuses and
switchgear.
Code
(hex) Fault / Aux. code
Cause
What to do
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...