94 Parameters
Measured output power in kW. The unit is selected by
. The filter time
constant can be adjusted by parameter
.
-
-32768.00… 32767.00
kW
Output power.
See par.
Measured output power in % of nominal motor
power.
-
-300.00… 300.00%
Output power.
10 = 1%
Estimated mechanical power at motor shaft in kW or
hp. Parameter
defines the unit.
The filter time constant can be adjusted by parameter
.
-
-32768.00… 32767.00
kW or hp
Motor shaft power.
See par.
Amount of energy that has passed through the drive
(in either direction) in full gigawatt-hours. The
minimum value is zero.
-
0…65535 GWh
Energy in GWh.
1 = 1 GWh
Amount of energy that has passed through the drive
(in either direction) in full megawatt-hours. Whenever
the counter rolls over,
incremented. The minimum value is zero.
-
0…1000 MWh
Energy in MWh.
1 = 1 MWh
Amount of energy that has passed through the drive
(in either direction) in full kilowatt-hours. Whenever
the counter rolls over,
incremented. The minimum value is zero.
-
0…1000 kWh
Energy in kWh.
10 = 1 kWh
Used flux reference in percent of nominal flux of
motor.
-
0…200%
Flux reference.
1 = 1%
Nominal torque in N•m which corresponds to 100%.
Note: This parameter is copied from parameter
if given. Otherwise the
value is calculated from other motor data.
0
0.000…4000000
N·m or lb·ft
Nominal torque.
1 = 100 unit
Current hour energy consumption. This is the energy
of the last 60 minutes (not necessarily continuous)
the drive has been running, not the energy of a
calendar hour. The value is set to the value before the
power cycle when the drive is again up and running.
- / -
0.00…1000000.00 kWh Energy.
1 = 1 kWh
Previous hour energy consumption. The value
Current
hour kWh
is stored here when its values has been
cumulated for 60 minutes. The value is set to the
value before the power cycle when the drive is again
up and running.
-
0.00…1000000.00 kWh Energy.
1 = 1 kWh
No.
Name/Value
Description
Default
FbEq 16
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...