Parameters 223
Defines the second underload point.
See parameter
15.0%
-1600.0…1600.0%
Underload point.
1 = 1%
Defines the third underload point.
See parameter
25.0%
-1600.0…1600.0%
Underload point.
1 = 1%
Defines the fourth underload point.
See parameter
30.0%
-1600.0…1600.0%
Underload point.
1 = 1%
Defines the fifth underload point.
See parameter
30.0%
-1600.0…1600.0%
Underload point.
1 = 1%
Defines the first of the five points on the Y-axis that
together with the corresponding point on the X-axis
…
or
37.15 ULC frequency table point
…
37.20 ULC frequency table point 5
) define the
overload (higher) curve.
At each of the five points the value of the underload
curve point must be equal to or smaller than the value
of the overload curve point. See parameter
.
300.0%
-1600.0…1600.0%
Overload point.
1 = 1%
Defines the second overload point.
See parameter
.
300.0%
-1600.0…1600.0%
Overload point.
1 = 1%
Defines the third overload point.
See parameter
.
300.0%
-1600.0…1600.0%
Overload point.
1 = 1%
Defines the fourth overload point.
See parameter
.
300.0%
-1600.0…1600.0%
Overload point.
1 = 1%
Defines the fifth overload point.
See parameter
.
300.0%
-1600.0…1600.0%
Overload point.
1 = 1%
Defines the time for which the monitored signal must
continuously stay above the overload curve before the
drive takes the action selected by
.
20.0 s
0.0…10000.0 s
Time.
1 = 1 s
Defines the time for which the monitored signal must
continuously stay below the underload curve before
the drive takes the action selected by
.
20.0 s
0.0…10000.0 s
Time.
1 = 1 s
No.
Name/Value
Description
Default
FbEq 16
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...