214 Parameters
Defines the motor load curve together with
parameters
. The load curve is used by the motor thermal
protection model to estimate the motor temperature.
When the parameter is set to 100%, the maximum
load is taken as the value of parameter
(higher loads heat up the motor). The
load curve level should be adjusted if the ambient
temperature differs from the nominal value set in
.
110%
50…150%
Maximum load for the motor load curve.
1 = 1%
Defines the motor load curve together with
parameters
and
. Defines the maximum motor load at zero speed
of the load curve. A higher value can be used if the
motor has an external motor fan to boost the cooling.
See the motor manufacturer's recommendations.
See parameter
.
70%
25…150%
Zero speed load for the motor load curve.
1 = 1%
Defines the motor load curve together with
parameters
and
. Defines the break point frequency of the
load curve ie. the point at which the motor load curve
begins to decrease from the value of parameter
towards the value of parameter
See parameter
.
45.00 Hz
1.00…500.00 Hz
Break point for the motor load curve.
See par.
No.
Name/Value
Description
Default
FbEq 16
50
100
150
I/I
N
(%)
I
= Motor current
I
N
= Nominal motor current
Drive output
frequency
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...