2-136
ACH550 E-Clipse Bypass User’s Manual
Embedded fieldbus
37
FLN CTL SRC
Indicates if FLN is a source for control inputs
(1 = YES, 0 = NO).
Note that this status point is true if any of the following control
inputs are from FLN: Run/Stop, Ext1/2 Select or Run Enable.
38
FLN REF1 SRC
Indicates if FLN is the source for speed reference 1
(1 = YES, 0 = NO).
39
FLN REF2 SRC
Indicates if FLN is the source for speed reference 2
(1 = YES, 0 = NO).
40
RO1 COMMAND Controls the output state of Relay 1.
Parameter 1401 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 0
41
RO2 COMMAND Controls the output state of Relay 2.
Parameter 1402 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 1
42
RO3 COMMAND Controls the output state of Relay 3.
Parameter 1403 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 2
43
RO4 COMMAND Controls the output state of Relay 4. Access to relay 4 require
ACH550 option OREL.
Parameter 1410 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 3
44
RO5 COMMAND Controls the output state of Relay 5. Access to relay 5 require
ACH550 option OREL.
Parameter 1411 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 4
45
RO6 COMMAND Controls the output state of Relay 6. Access to relay 6 require
ACH550 option OREL.
Parameter 1412 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 5
46
AO1 COMMAND Controls Analog Output 1.
Parameter 1501 must be set to this value for FLN to have this
control.
0135
(COMM
VALUE 1)
47
AO2 COMMAND Controls Analog Output 2.
Parameter 1507 must be set to this value for FLN to have this
control.
0136
(COMM
VALUE 2)
48
RESET RUN
TIME
Commanded by FLN to reset the cumulative run timer (1 =
RESET, 0 = NO).
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This “momentary” operation avoids any need
for an explicit command to clear the point before a
subsequent reset can be issued.
49
RESET KWH
Commanded by FLN to reset the cumulative kilowatt-hour
counter (1 = RESET, 0 = NO).
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This “momentary” operation avoids any need
for an explicit command to clear the point before a
subsequent reset can be issued.
FLN Detailed Point Descriptions
Point
Description
Drive
Parameter
Содержание ACH550-BCR
Страница 4: ...iv Manual contents ...
Страница 5: ...ACH550 UH User s Manual 1 1 ACH550 UH HVAC Drives 1 550 HP User s Manual 2016 ABB All Rights Reserved ...
Страница 6: ......
Страница 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Страница 36: ...1 32 ACH550 UH User s Manual Installation ...
Страница 70: ...1 66 ACH550 UH User s Manual Application macros ...
Страница 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Страница 348: ......
Страница 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Страница 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Страница 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Страница 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Страница 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Страница 608: ......
Страница 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Страница 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Страница 641: ......