0130
PID 1 FBK
Unit and scale defined
-
-
by par. 4006/4106 and
4007/4107
The
PID
1 controller feedback signal.
• Units and scale defined by PID parameters.
0131
PID 2 FBK
Unit and scale defined
-
-
by par. 4206 and 4207
The
PID
2 controller feedback signal.
• Units and scale defined by PID parameters.
0132
PID 1 DEVIATION
Unit and scale defined
-
-
by par. 4006/4106 and
4007/4107
The difference between the
PID
1 controller reference value and actual value.
• Units and scale defined by PID parameters.
0133
PID 2 DEVIATION
Unit and scale defined
-
-
by par. 4206 and 4207
The difference between the
PID
2 controller reference value and actual value.
• Units and scale defined by PID parameters.
0134
COMM RO WORD
0…65535
1
-
Free data location that can be written from serial link.
• Used for relay output control.
• See parameter 1401.
0135
COMM VALUE 1
-32768…+32767
1
-
Free data location that can be written from serial link.
0136
COMM VALUE 2
-32768…+32767
1
-
Free data location that can be written from serial link.
0137
PROCESS VAR 1
-
1
-
Process variable 1
• Defined by parameters in
.
0138
PROCESS VAR 2
-
1
-
Process variable 2
• Defined by parameters in
.
0139
PROCESS VAR 3
-
1
-
Process variable 3
• Defined by parameters in
.
0140
RUN TIME
0.00…499.99 kh
0.01 kh
-
The drive’s accumulated running time in thousands of hours (kh).
• Cannot be reset.
0141
MWH COUNTER
0…65535 MWh
1 MWh
-
The drive’s accumulated power consumption in megawatt hours.
• The counter value is accumulated till it reaches 65535 after which the counter rolls over and starts again from 0.
• Cannot be reset.
0142
REVOLUTION CNTR
0…65535 Mrev
1 Mrev
-
The motor’s accumulated revolutions in millions of revolutions.
• Can be reset by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0143
DRIVE ON TIME HI
0…65535 days
1 day
-
The drive’s accumulated power-on time in days.
• Cannot be reset.
Group 01: Operating Data
Code Description Range
Resolution
Default
S
Содержание ACH550-BCR
Страница 4: ...iv Manual contents ...
Страница 5: ...ACH550 UH User s Manual 1 1 ACH550 UH HVAC Drives 1 550 HP User s Manual 2016 ABB All Rights Reserved ...
Страница 6: ......
Страница 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Страница 36: ...1 32 ACH550 UH User s Manual Installation ...
Страница 70: ...1 66 ACH550 UH User s Manual Application macros ...
Страница 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Страница 348: ......
Страница 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Страница 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Страница 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Страница 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Страница 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Страница 608: ......
Страница 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Страница 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Страница 641: ......