![ABB ACH550-BCR Скачать руководство пользователя страница 248](http://html.mh-extra.com/html/abb/ach550-bcr/ach550-bcr_user-manual_2927248.webp)
1-244
ACH550-UH User’s Manual
Embedded fieldbus
The following table summarizes the 4xxxx drive control registers 40001…40099 (for
4xxxx registers above 40099, see the drive parameter list, e.g. 40102 is parameter 0102):
Modbus Register
Access
Remarks
4
0001
CONTROL
WORD
R/W
Maps directly to the profile‘
S
CONTROL
WORD
. Supported
only if 5305 = 0 or 2 (ABB Drives profile). Parameter
5319 holds a copy in hex format.
4
0002
Reference 1
R/W
Range = 0…+20000 (scaled to 0…1105
REF
1
MAX
), or
-20000…0 (scaled to 1105
REF
1
MAX
…0).
4
0003
Reference 2
R/W
Range = 0…+10000 (scaled to 0…1108
REF
2
MAX
), or
-10000…0 (scaled to 1108
REF
2
MAX
…0).
4
0004
STATUS
WORD
R
Maps directly to the profile‘
S
STATUS
WORD
. Supported
only if 5305 = 0 or 2 (ABB Drives profile). Parameter
5320 holds a copy in hex format.
4
0005
Actual 1
(select using 5310)
R
By default, stores a copy of 0103
OUTPUT
FREQ
. Use
parameter 5310 to select a different actual value for this
register.
4
0006
Actual 2
(select using 5311)
R
By default, stores a copy of 0104
CURRENT
. Use
parameter 5311 to select a different actual value for this
register.
4
0007
Actual 3
(select using 5312)
R
By default, stores nothing. Use parameter 5312 to
select an actual value for this register.
4
0008
Actual 4
(select by 5313)
R
By default, stores nothing. Use parameter 5313 to
select an actual value for this register.
4
0009
Actual 5
(select using 5314)
R
By default, stores nothing. Use parameter 5314 to
select an actual value for this register.
4
0010
Actual 6
(select using 5315)
R
By default, stores nothing. Use parameter 5315 to
select an actual value for this register.
4
0011
Actual 7
(select using 5316)
R
By default, stores nothing. Use parameter 5316 to
select an actual value for this register.
4
0012
Actual 8
(select using 5317)
R
By default, stores nothing. Use parameter 5317 to
select an actual value for this register.
4
0031
ACH550
CONTROL
WORD
LSW
R/W
Maps directly to the Least Significant Word of the DCU
profile‘s
CONTROL
WORD
. Supported only if 5305 = 1.
See parameter 0301.
4
0032
ACH550
CONTROL
WORD
MSW
R
Maps directly to the Most Significant Word of the DCU
profile‘s
CONTROL
WORD
. Supported only if 5305 = 1.
See parameter 0302.
4
0033
ACH550
STATUS
WORD
LSW
R
Maps directly to the Least Significant Word of the DCU
profile‘s
CONTROL
WORD
. Supported only if 5305 = 1.
See parameter 0303.
4
0034
ACH550
STATUS
WORD
MSW
R
Maps directly to the Most Significant Word of the DCU
profile‘s
CONTROL
WORD
. Supported only if 5305 = 1.
See parameter 0304.
40045
ACH550
REF
1 LSW
R/W
Maps directly to the Least Significant Word of the DCU
profile’s
REF
1. Supported only if BP Parameter
5305 = 1. See drive parameter 0111.
40046
ACH550
REF
1 MSW
R/W
Maps directly to the Most Significant Word of the DCU
profile’s
REF
1. Supported only if BP Parameter
5305 = 1. See drive parameter 0111.
Содержание ACH550-BCR
Страница 4: ...iv Manual contents ...
Страница 5: ...ACH550 UH User s Manual 1 1 ACH550 UH HVAC Drives 1 550 HP User s Manual 2016 ABB All Rights Reserved ...
Страница 6: ......
Страница 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Страница 36: ...1 32 ACH550 UH User s Manual Installation ...
Страница 70: ...1 66 ACH550 UH User s Manual Application macros ...
Страница 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Страница 348: ......
Страница 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Страница 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Страница 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...