1-104
ACH550-UH User’s Manual
Parameters
35 =
COMM
– Energize relay based on input from fieldbus communication.
• Fieldbus writes binary code in parameter 0134 that can energize relay 1…relay 6 according to the following:
• 0 = De-energize relay, 1 = Energize relay.
36 =
COMM
(-1) – Energize relay based on input from fieldbus communication.
• Fieldbus writes binary code in parameter 0134 that can energize relay 1…relay 6 according to the following:
• 0 = De-energize relay, 1 = Energize relay.
37 =
TIMED
FUNC
1 – Energize relay when Timed Function 1 is active. See
38…40 =
TIMED
FUNC
2…4 – Energize relay when Timed Function 2…4 is active. See
TIMED
FUNC
1 above.
41 =
MNT
TRIG
FAN
– Energize relay when cooling fan counter is triggered. See
.
42 =
MNT
TRIG
REV
– Energize relay when revolutions counter is triggered. See
.
43 =
MNT
TRIG
RUN
– Energize relay when run time counter is triggered. See
44 =
MNT
TRIG
MWH
– Energize relay when MWh counter is triggered. See
.
45 =
OVERRIDE
– Energize relay when override mode is active.
46 =
START
DELAY
– Energize relay when a start delay is active.
47 =
USER
LOAD
C
– Energize relay when a user load curve fault or alarm occurs.
1402
RELAY OUTPUT 2
0…47
1
2 (
RUN
)
Defines the event or condition that activates relay 2 – what relay output 2 means.
• See 1401
RELAY
OUTPUT
1.
1403
RELAY OUTPUT 3
0…47
1
3 [
FAULT
(-1)]
Defines the event or condition that activates relay 3 – what relay output 3 means.
• See 1401
RELAY
OUTPUT
1.
1404
RO 1 ON DELAY
0.0…3600.0 s
0.1 s
0.0 s
Defines the switch-on delay for relay 1.
• On / off delays are ignored when relay output 1401 is set to
PFA.
1405
RO 1 OFF DELAY
0.0…3600.0 s
0.1 s
0.0 s
Defines the switch-off delay for relay 1.
• On / off delays are ignored when relay output 1401 is set to PFA.
Group 14: Relay Outputs
Code Description Range
Resolution
Default
S
Par. 0134
Binary
RO6
RO5 RO4 RO3 RO2 RO1
0
000000
0
0
0
0
0
0
1
000001
0
0
0
0
0
1
2
000010
0
0
0
0
1
0
3
000011
0
0
0
0
1
1
4
000100
0
0
0
1
0
0
5…62
…
…
…
…
…
…
…
63
111111
1
1
1
1
1
1
Par. 0134 Binary
RO6
RO5 RO4 RO3 RO2 RO1
0
000000
1
1
1
1
1
1
1
000001
1
1
1
1
1
0
2
000010
1
1
1
1
0
1
3
000011
1
1
1
1
0
0
4
000100
1
1
1
0
1
1
5…62
…
…
…
…
…
…
…
63
111111
0
0
0
0
0
0
1404
ON
DELAY
1405
OFF
DELAY
Control event
Relay status
Содержание ACH550-BCR
Страница 4: ...iv Manual contents ...
Страница 5: ...ACH550 UH User s Manual 1 1 ACH550 UH HVAC Drives 1 550 HP User s Manual 2016 ABB All Rights Reserved ...
Страница 6: ......
Страница 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Страница 36: ...1 32 ACH550 UH User s Manual Installation ...
Страница 70: ...1 66 ACH550 UH User s Manual Application macros ...
Страница 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Страница 348: ......
Страница 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Страница 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Страница 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Страница 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Страница 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Страница 608: ......
Страница 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Страница 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Страница 641: ......