ACH550-UH User’s Manual
1-129
Parameters
3006
MOT THERM TIME
256…9999 s
1 s
1050 s
Sets the motor thermal time constant for the motor temperature
model.
• This is the time required for the motor to reach 63% of the final
temperature with steady load.
• For thermal protection according to UL requirements for NEMA
class motors, use the rule of thumb:
MOTOR
THERM
TIME
equals
35 times t6, where t6 (in seconds) is specified by the motor
manufacturer as the time that the motor can safely operate at
six times its rated current.
• The thermal time for a Class 10 trip curve is 350 s, for a Class
20 trip curve 700 s, and for a Class 30 trip curve 1050 s.
3007
MOT LOAD CURVE
50…150%
1%
100%
Sets the maximum allowable operating load of the motor.
• With the default value 100%, motor overload protection is
functioning when the constant current exceeds 127% of the
parameter 9906 MOTOR NOM CURR value.
• The default overloadability is at the same level as what motor
manufacturers typically allow below 30 °C (86 °F) ambient
temperature and below 1000 m (3300 ft) altitude. When the
ambient temperature exceeds 30 °C (86 °F) or the installation
altitude is over 1000 m (3300 ft), decrease the parameter 3007
value according to the motor manufacturer’s recommendation.
Example:
If the constant protection level needs to be 115% of
the motor nominal current, set parameter 3007 value to 91%
(= 115/127·100%).
3008
ZERO SPEED LOAD
25…150%
1%
70%
Sets the maximum allowable current at zero speed.
• Value is relative to 9906
MOTOR
NOM
CURR
.
3009
BREAK POINT FREQ
1…250 Hz
1 Hz
35 Hz
Sets the break point frequency for the motor load curve.
Example:
Thermal protection trip times when parameters 3006
MOT
THERM
TIME
, 3007
MOT
LOAD
CURVE
and 3008
ZERO
SPEED
LOAD
have default values.
Group 30: Fault Functions
Code Description Range
Resolution
Default
S
Temp. rise
100%
63%
}
P 3006
Motor load
t
t
Frequency
150
50
P 3007
P 3008
P 3009
100 =
127%
Output current relative to
9906
MOTOR
NOM
CURR
60 s
3.5
I
O
= Output current
I
N
= Nominal motor current
f
O
= Output frequency
f
BRK
= Break point frequency
A = Trip time
3.0
2.5
2.0
1.5
1.0
0.5
0
0
0.2
0.4
0.8
1.0
1.2
90 s
180 s
300 s
600 s
0.6
180 s
A
I
O
/
I
N
f
O
/
f
BRK
Содержание ACH550-BCR
Страница 4: ...iv Manual contents ...
Страница 5: ...ACH550 UH User s Manual 1 1 ACH550 UH HVAC Drives 1 550 HP User s Manual 2016 ABB All Rights Reserved ...
Страница 6: ......
Страница 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Страница 36: ...1 32 ACH550 UH User s Manual Installation ...
Страница 70: ...1 66 ACH550 UH User s Manual Application macros ...
Страница 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Страница 348: ......
Страница 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Страница 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Страница 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Страница 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Страница 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Страница 608: ......
Страница 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Страница 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Страница 641: ......