![ABB ACH550-BCR Скачать руководство пользователя страница 229](http://html.mh-extra.com/html/abb/ach550-bcr/ach550-bcr_user-manual_2927229.webp)
ACH550-UH User’s Manual
1-225
Embedded fieldbus
63
EXT PID FBCK
The External PID feedback signal.
0131
64
EXT PID DEV
The deviation of the External PID output signal from its
setpoint.
0133
65
N/A
66
SPD OUT MIN
Sets the minimum output speed of the drive as a percentage
of the motor nominal rating.
2007
(SCALAR)
2001
(SPEED)
67
SPD OUT MAX
Sets the maximum output speed of the drive as a percentage
of the motor nominal rating.
2008
(SCALAR)
2002
(SPEED)
68
FLN LOC CTL
Commanded by FLN to temporarily “steal” start/stop control
of the drive from its normal source and place it under FLN
control. This functionality is analogous to placing the drive in
HAND mode at the panel, with the control being taken by
FLN instead. HAND mode at the panel has priority over this
point. Thus, this point is only effective in temporarily taking
control from the digital inputs or some other internal control
functionality.
69
FLN LOC REF
Commanded by FLN to temporarily “steal” input reference
control of the drive from its normal source and place it under
FLN control. This functionality is analogous to placing the
drive in HAND mode at the panel, with the reference control
being taken by FLN instead. HAND mode at the panel has
priority over this point. Thus, this point is only effective in
temporarily taking control from the analog inputs or some
other internal control functionality.
70
DI 1 ACTUAL
Indicates the status of Digital Input 1 (1 = ON, 0 = OFF).
0118, bit 2
71
DI 2 ACTUAL
Indicates the status of Digital Input 2 (1 = ON, 0 = OFF).
0118, bit 1
72
DI 3 ACTUAL
Indicates the status of Digital Input 3 (1 = ON, 0 = OFF).
0118, bit 0
73
DI 4 ACTUAL
Indicates the status of Digital Input 4 (1 = ON, 0 = OFF).
0119, bit 2
74
DI 5 ACTUAL
Indicates the status of Digital Input 5 (1 = ON, 0 = OFF).
0119, bit 1
75
DI 6 ACTUAL
Indicates the status of Digital Input 6 (1 = ON, 0 = OFF).
0119, bit 0
76
RO 1 ACTUAL
Indicates the status of Relay Output 1 (1 = ON, 0 = OFF).
0122, bit 2
77
RO 2 ACTUAL
Indicates the status of Relay Output 2 (1 = ON, 0 = OFF).
0122, bit 1
78
RO 3 ACTUAL
Indicates the status of Relay Output 3 (1 = ON, 0 = OFF).
0122, bit 0
79
RO 4 ACTUAL
Indicates the status of Relay Output 4 (1 = ON, 0 = OFF).
0123, bit 2
80
RO 5 ACTUAL
Indicates the status of Relay Output 5 (1 = ON, 0 = OFF).
0123, bit 1
81
RO 6 ACTUAL
Indicates the status of Relay Output 6 (1 = ON, 0 = OFF).
0123, bit 0
82
AI 1 ACTUAL
Indicates the input level of Analog Input 1.
0120
83
AI 2 ACTUAL
Indicates the input level of Analog Input 2.
0121
84
AO 1 ACTUAL
Indicates the output level of Analog Output 1.
0124
85
AO 2 ACTUAL
Indicates the output level of Analog Output 2.
0125
FLN Detailed Point Descriptions
Point
Description
Drive
Parameter
Содержание ACH550-BCR
Страница 4: ...iv Manual contents ...
Страница 5: ...ACH550 UH User s Manual 1 1 ACH550 UH HVAC Drives 1 550 HP User s Manual 2016 ABB All Rights Reserved ...
Страница 6: ......
Страница 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Страница 36: ...1 32 ACH550 UH User s Manual Installation ...
Страница 70: ...1 66 ACH550 UH User s Manual Application macros ...
Страница 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Страница 348: ......
Страница 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Страница 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Страница 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Страница 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Страница 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Страница 608: ......
Страница 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Страница 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Страница 641: ......