2-226
ACH550 E-Clipse Bypass User’s Manual
Diagnostics
3006
UNDERVOLTAGE
Fault will be generated
only if the drive is
controlling the motor
and the power to the
bypass is removed
before the drive shuts
down. This fault is
generated when the
drive contactor opens
while the drive is
operating.
Loose J7 connector
on RBCU unit
Loose input wiring
Incoming power
problems
Check that J7
connector is firmly
seated in RBCU
Check tightness of
incoming connections
Check Parameter
0413 to view voltage
level at time of trip
Check upstream
protection
3008
DRIVE AI2 LOSS
Only displayed when
in Supervisory mode.
Indicates that AI2 on
the drive has failed.
Check ACH550
manual for AI2 loss
Check ACH550
manual for AI2 loss
3009
MTR OVERLOAD
Bypass opens on
motor overload
conditions defined in
the drive
Drive Mode:
Bad Motor
Bad CT’s
Bad RBCU
Bypass mode:
Bad motor
Bad CT’s
Bad RBCU
Either mode:
low input voltage
Check if overload
condition exists
Drive Mode:
Refer to 550 manual
for proper
troubleshooting
techniques
Bypass Mode:
Check that J2
connector is firmly
seated in RBCU
Use clamp meter to
verify mtr current vs.
display in parameter
0101
Check input voltage
3010
INP PHASE A
LOSS
Fault will be generated
when the bypass
contactor is requested
to be closed and the
RBCU does not sense
voltage on Phase A
Loose J7 connector
Loose wiring on
Contactor assembly.
Blown upstream fuse
Check J7 connector
Check yellow wire on
input block
Check incoming
voltage, phase to
ground
3011
INP PHASE B
LOSS
Fault will be generated
when the bypass
contactor is requested
to be closed and the
RBCU does not sense
voltage on Phase B
Loose J7 connector
Loose wiring on
Contactor assembly.
Blown upstream fuse
Check J7 connector
Check black wire on
input block
Check incoming
voltage, phase to
ground
3012
INP PHASE C
LOSS
Fault will be generated
when the bypass
contactor is requested
to be closed and the
RBCU does not sense
voltage on Phase C
Loose J7 connector
Loose wiring on
Contactor assembly.
Blown upstream fuse
Check J7 connector
Check red on input
block
Check incoming
voltage, phase to
ground
Fault
Code
Fault Name In
Panel
Fault
Possible Cause
Corrective Action
Содержание ACH550-BCR
Страница 4: ...iv Manual contents ...
Страница 5: ...ACH550 UH User s Manual 1 1 ACH550 UH HVAC Drives 1 550 HP User s Manual 2016 ABB All Rights Reserved ...
Страница 6: ......
Страница 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Страница 36: ...1 32 ACH550 UH User s Manual Installation ...
Страница 70: ...1 66 ACH550 UH User s Manual Application macros ...
Страница 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Страница 348: ......
Страница 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Страница 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Страница 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Страница 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Страница 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Страница 608: ......
Страница 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Страница 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Страница 641: ......