ACH550 E-Clipse Bypass User’s Manual
Embedded fieldbus
Detailed point descriptions – bypass
FLN Detailed Point Descriptions
Point
Description
Drive
Parameter
1
CTRL ADDRESS The FLN address of the bypass. It can be set by FLN and by
the panel.
5002
2
APPLICATION
This is the Application ID for FLN on the E-Clipse Bypass.
This ID is assigned by Siemens for each unique application.
It correlates directly to a particular point list approved at the
time of release. Therefore, this point list shall remain fixed
once approval is granted. Any changes to the point list shall
require a new Application ID and re-approval by Siemens.
The Application ID assigned to the E-Clipse bypass is 2737.
{5}
INPUT VOLT
Average of line-line input voltage
0102
{6}
CURRENT
Measured output current.
0101
{7}
SYS
UNDRLOAD
This point indicates if the system is in an underload
condition. Detection of this condition is done with bypass
parameters 3001-3003.
{9}
PCB TEMP
DEG C of bypass board
0105
10
KW HOURS
Bypass-mode kilowatt hours
0106
12
RUN TIME
Bypass mode run hours
0108
13
A-B VOLT
Phase A - Phase B voltage
0111
14
B-C VOLT
Phase B - Phase C voltage
0112
15
C-A VOLT
Phase C - Phase A voltage
0113
20
OVRD TIME
This is 1 of 5 mandatory FLN points required for
compatibility with Siemens control systems. It has no
functionality in the bypass application.
{23} MTR RUNNING
This point indicates the system’s run status, regardless of
control source (1 = RUN, 0 = STOP).
{24} RUN.STOP CMD This point is commanded by FLN to start the system.
Bypass parameter 1601 must be set to COMM for FLN to
control the run state of the system.
{25} OVERRIDE ACT
This point indicates if the bypass is in override 1 or override
2.
{26} OVERRID CMD
This point is commanded by FLN to select override 2.
Override 2 is configured by parameters in bypass group 17.
{27} SYSTEM
READY
This point indicates the system is ready to accept a run
command (1 = READY, 0 = NOTRDY).
{28} SYS STARTED
This point the system has received a run command and is
started. It may or may not be running based on the RUN
ENABLE status.
{29} DAY.NIGHT
This is 1 of 5 mandatory FLN points required for
compatibility with Siemens control systems. It has no
functionality in the bypass application.
30
BYP RUN DLY
This allows FLN to delay running of the system after a run
command has been issued.
1614
{31} BYPASS MODE
This point indicates the Hand/Off/Auto status of the bypass.
0=OFF; 1=HAND; 2=AUTO.
Содержание ACH550-BCR
Страница 4: ...iv Manual contents ...
Страница 5: ...ACH550 UH User s Manual 1 1 ACH550 UH HVAC Drives 1 550 HP User s Manual 2016 ABB All Rights Reserved ...
Страница 6: ......
Страница 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Страница 36: ...1 32 ACH550 UH User s Manual Installation ...
Страница 70: ...1 66 ACH550 UH User s Manual Application macros ...
Страница 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Страница 348: ......
Страница 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Страница 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Страница 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Страница 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Страница 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Страница 608: ......
Страница 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Страница 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Страница 641: ......