![ABB ACH550-BCR Скачать руководство пользователя страница 150](http://html.mh-extra.com/html/abb/ach550-bcr/ach550-bcr_user-manual_2927150.webp)
1-146
ACH550-UH User’s Manual
Parameters
3626
TIMER 1 SRC
0…31
1
0 (
NOT
SEL
)
Defines the time periods used by the timer.
0 =
NOT
SEL
– No time periods have been selected.
1 =
P
1 – Time Period 1 selected in the timer.
2 =
P
2 – Time Period 2 selected in the timer.
3 =
P
1+
P
2 – Time Periods 1 and 2 selected in the timer.
4 =
P
3 – Time Period 3 selected in the timer.
5 =
P
1+
P
3 – Time Periods 1 and 3 selected in the timer.
6 =
P
2+
P
3 – Time Periods 2 and 3 selected in the timer.
7 =
P
1+
P
2+
P
3 – Time Periods 1, 2 and 3 selected in the timer.
8 =
P
4 – Time Period 4 selected in the timer.
9 =
P
1+
P
4 – Time Periods 1 and 4 selected in the timer.
10 =
P
2+
P
4 – Time Periods 2 and 4 selected in the timer.
11 =
P
1+
P
2+
P
4 – Time Periods 1, 2 and 4 selected in the timer.
12 =
P
3+
P
4 – Time Periods 3 and 4 selected in the timer.
13 =
P
1+
P
3+
P
4 – Time Periods 1, 3 and 4 selected in the timer.
14 =
P
2+
P
3+
P
4 – Time Periods 2, 3 and 4 selected in the timer.
15 =
P
1+
P
2+
P
3+
P
4 – Time Periods 1, 2, 3 and 4 selected in the timer.
16 =
BOOSTER
– Booster selected in the timer.
17 =
P
1+
B
– Booster and Time Period 1 selected in the timer.
18 =
P
2+
B
– Booster and Time Period 2 selected in the timer.
19 =
P
1+
P
2+
B
– Booster and Time Periods 1 and 2 selected in the timer.
20 =
P
3+
B
– Booster and Time Period 3 selected in the timer.
21 =
P
1+
P
3+
B
– Booster and Time Periods 1 and 3 selected in the timer.
22 =
P
2+
P
3+
B
– Booster and Time Periods 2 and 3 selected in the timer.
23 =
P
1+
P
2+
P
3+
B
– Booster and Time Periods 1, 2 and 3 selected in the timer.
24 =
P
4+
B
– Booster and Time Period 4 selected in the timer.
25 =
P
1+
P
4+
B
– Booster and Time Periods 1 and 4 selected in the timer.
26 =
P
2+
P
4+
B
– Booster and Time Periods 2 and 4 selected in the timer.
27 =
P
1+
P
2+
P
4+
B
– Booster and Time Periods 1, 2 and 4 selected in the timer.
28 =
P
3+
P
4+
B
– Booster and Time Periods 3 and 4 selected in the timer.
29 =
P
1+
P
3+
P
4+
B
– Booster and Time Periods 1, 3 and 4 selected in the timer.
30 =
P
2+
P
3+
P
4+
B
– Booster and Time Periods 2, 3 and 4 selected in the timer.
31 =
P
1+2+3+4+
B
– Booster and Time Periods 1, 2, 3 and 4 selected in the timer.
3627
TIMER 2 SRC
0…31
1
0 (
NOT
SEL
)
• See parameter 3626.
3628
TIMER 3 SRC
0…31
1
0 (
NOT
SEL
)
• See parameter 3626.
3629
TIMER 4 SRC
0…31
1
0 (
NOT
SEL
)
• See parameter 3626.
Group 36: Timed Functions
Code Description Range
Resolution
Default
S
Содержание ACH550-BCR
Страница 4: ...iv Manual contents ...
Страница 5: ...ACH550 UH User s Manual 1 1 ACH550 UH HVAC Drives 1 550 HP User s Manual 2016 ABB All Rights Reserved ...
Страница 6: ......
Страница 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Страница 36: ...1 32 ACH550 UH User s Manual Installation ...
Страница 70: ...1 66 ACH550 UH User s Manual Application macros ...
Страница 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Страница 348: ......
Страница 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Страница 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Страница 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Страница 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Страница 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Страница 608: ......
Страница 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Страница 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Страница 641: ......