![ABB ACH550-BCR Скачать руководство пользователя страница 131](http://html.mh-extra.com/html/abb/ach550-bcr/ach550-bcr_user-manual_2927131.webp)
ACH550-UH User’s Manual
1-127
Parameters
Group 29: MAINTENANCE TRIG
This group contains usage levels and trigger points. When usage reaches the set
trigger point, a notice displayed on the control panel signals that maintenance is due.
Group 29: Maintenance Trig
Code Description Range
Resolution
Default
S
2901
COOLING FAN TRIG
0.0…6553.5 kh
0.1 kh
0.0 kh
0.0 disables
Sets the trigger point for the drive’s cooling fan counter.
• Value is compared to parameter 2902 value.
0.0 – Disables the trigger.
2902
COOLING FAN ACT
0.0…6553.5 kh
0.1 kh
0.0 kh
Defines the actual value of the drive’s cooling fan counter.
• When parameter 2901 has been set to a non-zero value, the counter starts.
• When the actual value of the counter exceeds the value defined by parameter 2901, a maintenance notice is
displayed on the panel.
0.0 – Resets the parameter.
2903
REVOLUTION TRIG
0…65535 Mrev
1 Mrev
0 Mrev
0 disables
Sets the trigger point for the motor’s accumulated revolutions counter.
• Value is compared to parameter 2904 value.
0 – Disables the trigger.
2904
REVOLUTION ACT
0…65535 Mrev
1 Mrev
0 Mrev
Defines the actual value of the motor’s accumulated revolutions counter.
• When parameter 2903 has been set to a non-zero value, the counter starts.
• When the actual value of the counter exceeds the value defined by parameter 2903, a maintenance notice is
displayed on the panel.
0 – Resets the parameter.
2905
RUN TIME TRIG
0.0…6553.5 kh
0.1 kh
0.0 kh
0.0 disables
Sets the trigger point for the drive’s run time counter.
• Value is compared to parameter 2906 value.
0.0 – Disables the trigger.
2906
RUN TIME ACT
0.0…6553.5 kh
0.1 kh
0.0 kh
Defines the actual value of the drive’s run time counter.
• When parameter 2905 has been set to a non-zero value, the counter starts.
• When the actual value of the counter exceeds the value defined by parameter 2905, a maintenance notice is
displayed on the panel.
0.0 – Resets the parameter.
2907
USER MWh TRIG
0.0…6553.5 MWh
0.1 MWh
0.0 MWh
0.0 disables
Sets the trigger point for the drive’s accumulated power consumption (in megawatt hours) counter.
• Value is compared to parameter 2908 value.
0.0 – Disables the trigger.
2908
USER MWh ACT
0.0…6553.5 MWh
0.1 MWh
0.0 MWh
Defines the actual value of the drive’s accumulated power consumption (in megawatt hours) counter.
• When parameter 2907
has been set to a non-zero value, the counter starts.
• When the actual value of the counter exceeds the value defined by parameter 2907, a maintenance notice is
displayed on the panel.
0.0 – Resets the parameter.
Содержание ACH550-BCR
Страница 4: ...iv Manual contents ...
Страница 5: ...ACH550 UH User s Manual 1 1 ACH550 UH HVAC Drives 1 550 HP User s Manual 2016 ABB All Rights Reserved ...
Страница 6: ......
Страница 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Страница 36: ...1 32 ACH550 UH User s Manual Installation ...
Страница 70: ...1 66 ACH550 UH User s Manual Application macros ...
Страница 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Страница 348: ......
Страница 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Страница 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Страница 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Страница 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Страница 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Страница 608: ......
Страница 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Страница 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Страница 641: ......