Group 25: CRITICAL SPEEDS
This group defines up to three critical speeds or ranges of speeds that are to be
avoided due, for example, to mechanical resonance problems at certain speeds.
Group 25: Critical Speeds
Code Description Range
Resolution
Default
S
2501
CRIT SPEED SEL
0, 1
1
0 (
OFF
)
Sets the critical speeds function on or off. The critical speed
function avoids specific speed ranges.
0 =
OFF
– Disables the critical speeds function.
1 =
ON
– Enables the critical speeds function.
Example:
To avoid speeds at which a fan system vibrates
badly:
• Determine problem speed ranges. Assume they are found to
be: 18…23 Hz and 46…52 Hz.
• Set 2501
CRIT
SPEED
SEL
= 1.
• Set 2502
CRIT
SPEED
1
LO
= 18 Hz.
• Set 2503
CRIT
SPEED
1
HI
= 23 Hz.
• Set 2504
CRIT
SPEED
2
LO
= 46 Hz.
• Set 2505
CRIT
SPEED
2
HI
= 52 Hz.
2502
CRIT SPEED 1 LO
0.0…500.0 Hz /
0.1 Hz /
0.0 Hz /
0…30000 rpm
1 rpm
0 rpm
Sets the minimum limit for critical speed range 1.
• The value must be less than or equal to 2503
CRIT
SPEED
1
HI
.
• Units are rpm, unless 9904
MOTOR
CTRL
MODE
= 3 (
SCALAR
:
FREQ
), then units are Hz.
2503
CRIT SPEED 1 HI
0.0…500.0 Hz /
0.1 Hz /
0.0 Hz /
0…30000 rpm
1 rpm
0 rpm
Sets the maximum limit for critical speed range 1.
• The value must be greater than or equal to 2502
CRIT
SPEED
1
LO
.
• Units are rpm, unless 9904
MOTOR
CTRL
MODE
= 3 (
SCALAR
:
FREQ
), then units are Hz.
2504
CRIT SPEED 2 LO
0.0…500.0 Hz /
0.1 Hz /
0.0 Hz /
0…30000 rpm
1 rpm
0 rpm
Sets the minimum limit for critical speed range 2.
• See parameter 2502.
2505
CRIT SPEED 2 HI
0.0…500.0 Hz /
0.1 Hz /
0.0 Hz /
0…30000 rpm
1 rpm
0 rpm
Sets the maximum limit for critical speed range 2.
• See parameter 2503.
2506
CRIT SPEED 3 LO
0.0…500.0 Hz /
0.1 Hz /
0.0 Hz /
0…30000 rpm
1 rpm
0 rpm
Sets the minimum limit for critical speed range 3.
• See parameter 2502.
2507
CRIT SPEED 3 HI
0.0…500.0 Hz /
0.1 Hz /
0.0 Hz /
0…30000 rpm
1 rpm
0 rpm
Sets the maximum limit for critical speed range 3.
• See parameter 2503.
52
46
23
18
f1L
18
f2L
46
f1H
23
f2H
52
f
output
f
REF
(Hz)
Содержание ACH550-BCR
Страница 4: ...iv Manual contents ...
Страница 5: ...ACH550 UH User s Manual 1 1 ACH550 UH HVAC Drives 1 550 HP User s Manual 2016 ABB All Rights Reserved ...
Страница 6: ......
Страница 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Страница 36: ...1 32 ACH550 UH User s Manual Installation ...
Страница 70: ...1 66 ACH550 UH User s Manual Application macros ...
Страница 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Страница 348: ......
Страница 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Страница 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Страница 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Страница 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Страница 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Страница 608: ......
Страница 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Страница 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Страница 641: ......