1-224
ACH550-UH User’s Manual
Embedded fieldbus
46
AO1 COMMAND Controls Analog Output 1.
Parameter 1501 must be set to this value for FLN to have this
control.
0135
(COMM
VALUE 1)
47
AO2 COMMAND Controls Analog Output 2.
Parameter 1507 must be set to this value for FLN to have this
control.
0136
(COMM
VALUE 2)
48
RESET RUN
TIME
Commanded by FLN to reset the cumulative run timer (1 =
RESET, 0 = NO).
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This “momentary” operation avoids any need
for an explicit command to clear the point before a
subsequent reset can be issued.
49
RESET KWH
Commanded by FLN to reset the cumulative kilowatt-hour
counter (1 = RESET, 0 = NO).
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This “momentary” operation avoids any need
for an explicit command to clear the point before a
subsequent reset can be issued.
50
PRC PID GAIN
Sets the proportional gain of the active Process PID set, as
selected by Point 54, PRC PID SEL (1 = SET2, 0 = SET1).
4001 (SET1)
4101 (SET2)
51
PRC PID ITIM
Sets the integration time of the active Process PID set, as
selected by Point 54, PRC PID SEL (1 = SET2, 0 = SET1).
4002 (SET1)
4102 (SET2)
52
PRC PID DTIM
Sets the derivation time of the active Process PID set, as
selected by Point 54, PRC PID SEL (1 = SET2, 0 = SET1).
4001 (SET1)
4101 (SET2)
53
PRC PID DFIL
Sets the time constant for the error-derivative of the active
Process PID set, as selected by Point 54, PRC PID SEL
(1 = SET2, 0 = SET1).
4004 (SET1)
4104 (SET2)
54
PRC PID SEL
Selects the active Process PID set (1 = SET2, 0 = SET1).
4027
55
EXT PID GAIN
Sets the proportional gain of the External PID controller.
4201
56
EXT PID ITIM
Sets the integration time of the External PID controller.
4202
57
EXT PID DTIM
Sets the derivation time of the External PID controller.
4203
58
EXT PID DFIL
Sets the time constant for the error-derivative of the External
PID controller.
4204
59
LOCK PANEL
Command by FLN to lock the panel and prevent parameter
changes (1 = LOCK, 0 = UNLOCK).
1602
60
INPUT REF 1
Sets Input Reference 1.
Parameter 1102 must be set to COMM for FLN to control this
value.
61
INPUT REF 2
Sets Input Reference 2.
Parameter 1106 must be set to COMM for FLN to control this
value.
62
EXT PID STPT
The setpoint for the External PID controller.
The function of this point requires parameter 4210, PID
Setpoint Select, to be set to 19 (Internal).
4211
FLN Detailed Point Descriptions
Point
Description
Drive
Parameter
Содержание ACH550-BCR
Страница 4: ...iv Manual contents ...
Страница 5: ...ACH550 UH User s Manual 1 1 ACH550 UH HVAC Drives 1 550 HP User s Manual 2016 ABB All Rights Reserved ...
Страница 6: ......
Страница 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Страница 36: ...1 32 ACH550 UH User s Manual Installation ...
Страница 70: ...1 66 ACH550 UH User s Manual Application macros ...
Страница 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Страница 348: ......
Страница 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Страница 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Страница 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Страница 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Страница 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Страница 608: ......
Страница 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Страница 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Страница 641: ......