2-234
ACH550 E-Clipse Bypass User’s Manual
Diagnostics
4016
INP VOLTAGE
LOW
3-Phase input voltage
has not reached a
sufficient level to
enable editing of
parameters via the
keypad. This message
is generated within a
few seconds of power
up
NA
Loose J7 connector
Low input voltage.
Incoming voltage has
not reached at least
155 VAC within a few
seconds of powerup
4019
OVERRIDE 1
Alarm is generated
when override 1 is
active
NA
Check Parameter
0103 and 0104 for
digital input status
4020
OVRD2 BYP
Alarm is generated
when override 2 is
active and the bypass
is controlling the motor
NA
Check Parameter
0103 and 0104 for
digital input status
4021
Selected by PAR
1621
START ENABLE 1
VIBRATION
SWITCH
FIRESTAT
FREEZESTAT
OVERPRESSURE
VIBRATION TRIP
SMOKE ALARM
SAFETY OPEN
LOW SUCTION
PRES
Alarm will occur when
start order is given and
the “RUN Enable” is not
present
Run Enable condition is
not satisfied.
Bad 24v supply
Bad digital input
24 V common is not
tied to Digital input
common on bypass
when using external 24
v supply
Check 24 Volts on
RBCU unit
Check for 24 volts on
respective DI when
condition is satisfied
Check Parameter 0103
For status of digital
input
4022
Selected by PAR
1622
START ENABLE 2
VIBRATION
SWITCH
...
LOW SUCTION
PRES
Alarm will occur when
start order is given and
the “RUN Enable” is not
present
Run Enable condition is
not satisfied.
Bad 24v supply
Bad digital input
24 V common is not
tied to Digital input
common on bypass
when using external 24
v supply
Check 24 Volts on
RBCU unit
Check for 24 volts on
respective DI when
condition is satisfied
Check Parameter 0103
For status of digital
input
4023
Selected by PAR
1623
START ENABLE 3
VIBRATION
SWITCH
...
LOW SUCTION
PRES
Alarm will occur when
start order is given and
the “RUN Enable” is not
present
Run Enable condition is
not satisfied.
Bad 24v supply
Bad digital input
24 V common is not
tied to Digital input
common on bypass
when using external 24
v supply
Check 24 Volts on
RBCU unit
Check for 24 volts on
respective DI when
condition is satisfied
Check Parameter 0103
For status of digital
input
Alarm
Code
Alarm Name In
Panel
Alarm
Possible Cause
Corrective Action
Содержание ACH550-BCR
Страница 4: ...iv Manual contents ...
Страница 5: ...ACH550 UH User s Manual 1 1 ACH550 UH HVAC Drives 1 550 HP User s Manual 2016 ABB All Rights Reserved ...
Страница 6: ......
Страница 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Страница 36: ...1 32 ACH550 UH User s Manual Installation ...
Страница 70: ...1 66 ACH550 UH User s Manual Application macros ...
Страница 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Страница 348: ......
Страница 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Страница 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Страница 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Страница 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Страница 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Страница 608: ......
Страница 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Страница 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Страница 641: ......